Biofouling reduction in recirculating cooling systems through biofiltration of process water
K P H Meesters1, J W Van Groenestijn, J Gerritse
1TNO Environment, Energy and Process Innovation, P.O. Box 342, 7300 AH Apeldoorn, The Netherlands.
Water Research
|April 12, 2003
Summary
A novel biofilter effectively removes assimilable organic carbon (AOC) from industrial cooling water, significantly reducing biofouling. This environmentally friendly method lowers bacterial growth and improves system efficiency.
Area of Science:
- Environmental Engineering
- Industrial Microbiology
- Water Treatment Technologies
Background:
- Biofouling poses significant challenges in industrial recirculating cooling systems, leading to equipment damage (biocorrosion) and reduced efficiency (clogging, decreased heat transfer).
- Assimilable organic carbon (AOC) in process water serves as a primary nutrient source for microbial growth, driving biofouling processes.
Purpose of the Study:
- To develop and evaluate a fixed-bed biofilter for removing AOC from industrial cooling water.
- To assess the efficacy of biofiltration in mitigating biofouling in a model recirculating cooling water system.
Main Methods:
- A fixed-bed biofilter was integrated into a laboratory model recirculating cooling water system with a heat exchanger and cooling tower.
- The system was challenged with organic carbon (sucrose, yeast extract) to induce biofouling, with a parallel system without a biofilter serving as a reference.
- Key water quality parameters (AOC, ATP, bacterial numbers, turbidity) and biofouling indicators (protein, heat transfer resistance, chlorine demand) were monitored.
Main Results:
- The biofilter significantly reduced AOC content, ATP concentration, bacterial numbers (30-40 fold reduction), and turbidity (OD660) in the cooling water.
- Biofouling was substantially lower in the system equipped with the biofilter compared to the reference system.
- Improvements were observed in heat exchanger performance and reduced maintenance chlorine demand.
Conclusions:
- AOC removal via biofiltration is an effective and environmentally friendly strategy for controlling biofouling in industrial recirculating cooling systems.
- Biofiltration offers a sustainable approach to enhance operational efficiency and prolong equipment lifespan in cooling water applications.