Related Experiment Video
Updated: Feb 8, 2026

Preparation of Free-Surface Hyperbolic Water Vortices
Published on: July 28, 2023
Estimation of Giardia Ct values at high pH for the Surface Water Treatment Rule
Mano Sivaganesan1, Eugene W Rice
1Office of the Director, Water Supply and Water Resources Division, National Risk Management Research Laboratory, U.S. Environmental Protection Agency, Cincinnati, Ohio, USA. sivaganesan.mano@epa.gov
Abstract:
The U.S. Environmental Protection Agency currently recommends Ct (disinfectant concentration multiplied by the exposure time) values to achieve required levels of inactivation of Giardia lamblia cysts by different disinfectants including free chlorine. Current guidance covers inactivation levels in the pH range between 6 and 9. Subsequent to the publication of these criteria, studies on the inactivation kinetics of Giardia cysts by chlorine have been performed at pH levels greater than 9. It has been shown that the chlorine inactivation process for Giardia cysts is pH dependent. The objective of this paper is to extend the current Ct values for higher pH levels. The Chick-Watson first order kinetics model was used to develop Ct values for pH levels from 6 to 11.5. A formula is provided to calculate a 100(1 - alpha)% upper confidence bound for these values.