Human response to personalized ventilation and mixing ventilation.
J Kaczmarczyk1, A Melikov, P O Fanger
1International Center for Indoor Environment and Energy, Technical University of Denmark, Kgs Lyngby, Denmark. jk@mek.dtu.dk
Indoor Air
|January 25, 2005
Summary
Personalized ventilation systems (PVS) enhance occupant comfort and perceived air quality compared to traditional mixing ventilation (MV). PVS improved thermal comfort and reduced Sick Building Syndrome symptoms, leading to better self-estimated performance.
Area of Science:
- Building Science
- Environmental Health
- Human Factors Engineering
Background:
- Traditional mixing ventilation (MV) systems often fail to meet diverse occupant needs for thermal comfort and air quality.
- Personalized ventilation systems (PVS) offer individual control over microclimate conditions.
Purpose of the Study:
- To compare the effectiveness of a personalized ventilation system (PVS) against mixing ventilation (MV).
- To evaluate occupant responses in terms of perceived air quality, thermal comfort, Sick Building Syndrome (SBS) symptoms, and performance.
Main Methods:
- Sixty human subjects were exposed to either PVS or MV for 3 hours and 45 minutes.
- PVS allowed individual control of air terminal device positioning and airflow rate.
- Room air temperatures were maintained at 23°C and 26°C for comparison.
Main Results:
- PVS significantly improved perceived air quality and reduced SBS symptoms compared to MV.
- The percentage of dissatisfied occupants regarding air quality decreased from 22% with MV to 7% with PVS at 23°C.
- Headache and cognitive clarity issues were least intense with PVS using outdoor air at 20°C; PVS also increased self-estimated performance.
Conclusions:
- Personalized ventilation systems offer superior thermal comfort and perceived air quality over mixing ventilation.
- Occupants effectively utilize PVS controls to achieve preferred microenvironments within standard indoor climate ranges.
- Further development of efficient air terminal devices for PVS is recommended.