Aspergillus surveillance project at a large tertiary-care hospital

L Curtis1, S Cali, L Conroy

  • 1Department of Environmental and Occupational Health Science, University of Illinois at Chicago, Chicago, IL 60612, USA. lukec@uic.edu

Insights

Hospital renovations and nearby construction increased indoor Aspergillus levels, posing risks to patients. Monitoring detected Aspergillus niger and Aspergillus fumigatus, highlighting the need for better environmental controls in healthcare settings.

Area of Science:

  • Environmental microbiology
  • Hospital infection control
  • Air quality monitoring

Background:

  • Hospital renovations and nearby construction activities can potentially impact indoor air quality.
  • Fungal contamination, particularly Aspergillus species, is a concern in healthcare environments, especially for immunocompromised patients.

Purpose of the Study:

  • To conduct a one-year surveillance of viable fungi and Aspergillus species in a tertiary hospital.
  • To analyze Aspergillus fumigatus specific marker (asp f1 protein) in duct dust.
  • To identify sources and incidents contributing to elevated Aspergillus levels.

Main Methods:

  • Collected viable fungi samples bi-weekly over one year.
  • Analyzed 74 duct dust samples for Aspergillus fumigatus asp f1 protein.
  • Compared indoor fungal concentrations with outdoor levels and identified specific Aspergillus species.

Main Results:

  • Indoor Aspergillus levels were higher than outdoor levels.
  • Aspergillus niger was the most prevalent species, followed by Aspergillus candidus, Aspergillus flavus, Aspergillus fumigatus, and Aspergillus glaucus.
  • Elevated Aspergillus concentrations were linked to specific incidents: water leaks, HEPA filter infiltration, and renovation activities like wood cutting.

Conclusions:

  • The study identified multiple sources of Aspergillus contamination within the hospital environment.
  • Renovation, water damage, and compromised air filtration systems significantly contribute to increased Aspergillus levels.
  • Enhanced environmental monitoring and control measures are crucial for patient safety in healthcare facilities undergoing construction or renovation.