Related Experiment Video
Updated: Aug 11, 2026

Design and Optimization Strategies of a High-Performance Vented Box
Published on: June 9, 2023
Numerical investigation of airflow pattern and particulate matter transport in naturally ventilated multi-room
T-J Chang1, Y-F Hsieh, H-M Kao
1Department of Bioenvironmental Systems Engineering, National Taiwan University, Taipei, Taiwan. tjchang@ntu.edu.tw
Unlabelled:
This study reports on a numerical investigation of transport behavior of indoor airflow and size-dependent particulate matter (PM) in multi-room buildings. An indoor size-dependent PM transport approach, combining the Eulerian large-eddy simulation of turbulent flow with the Lagrangian particle trajectory tracking, was developed to investigate indoor airflow pattern and PM1/PM2.5/PM10 removal efficiency in naturally ventilated multi-room buildings. A displacement ventilation with a measured indoor PM10 profile in Taipei Metropolis as the initial condition was carried out to characterize spatial and temporal variations of indoor PM1/PM2.5/PM10 removal behavior. The effects of indoor airflow pattern on particle transport mechanisms, e.g., deposition, suspension, migration and escape, were analyzed. Two comparison scenarios, which considered the effects of no indoor partition and different air change rate, respectively, were also conducted. In comparison with the effectiveness of PM1/PM2.5/PM10 removal, the simulated results showed that coarse particles were easier to be removed out of the building than fine particles. Natural ventilation was not an effective way to remove fine particles such as PM1 and PM2.5 in a multi-room building. Indoor partitions can impede 12% of the mean streamwise velocities and significantly increase 30-50% turbulence intensities. However, indoor partitions increased particle deposition and decreased particle escape. As a result of the two opposite particle removal mechanisms, i.e., deposition and escape, the impact of indoor partitions on PM1/PM2.5/PM10 removal behavior was not as significant as the results of airflow velocities.
Practical Implications:
This work developed a computational fluid dynamics technique to investigate indoor airflow patterns and PM1/PM2.5/PM10 removal ability in ventilated multi-room buildings. The results of this paper can help to identify adequate PM1/PM2.5/PM10 cleaning procedure and provide useful size-dependent PM control strategy in multi-room buildings.
More Related Videos
09:33Visualizing Field Data Collection Procedures of Exposure and Biomarker Assessments for the Household Air Pollution Intervention Network Trial in India
Published on: December 23, 2022
07:12Façade-Level Monitoring of CO2 Variability under Urban Heat Island Conditions using Low-Cost Sensor Data Loggers
Published on: December 12, 2025
Related Concept Videos
Factors Affecting Pulmonary Ventilation
Alveolar Surface Tension
The alveolar fluid lines the luminal surface of the alveoli and exerts a force called surface tension. This force is caused by the polar water molecules in the liquid being more strongly attracted to each...
Assessment of Ventilation I: Respiratory Rate
A Ventilation assessment is critical for monitoring a patient's health status. Respiration, one of the most accessible vital signs, provides insights into the function of numerous body systems and can indicate serious health issues, such as brainstem injuries from head trauma.
Critical Guidelines for Assessing Ventilation:
Application of Integration: Problem Solving
Respiratory Volumes and Capacities