Related Experiment Video
Updated: Aug 10, 2026

In Situ Gas Analysis and Fire Characterization of Lithium-Ion Cells During Thermal Runaway Using an Environmental Chamber
Published on: March 31, 2023
Incident analysis of Bucheon LPG filling station pool fire and BLEVE
Kyoshik Park1, M Sam Mannan, Young-Do Jo
1Institute of Gas Safety R&D, Korea Gas Safety Corporation, 332-1 Daeya-dong, Siheung-shi, Gyeonggi-do, South Korea. kspark@kgs.or.kr
Abstract:
An LPG filling station incident in Korea has been studied. The direct cause of the incident was concluded to be faulty joining of the couplings of the hoses during the butane unloading process from a tank lorry into an underground storage tank. The faulty connection of a hose to the tank lorry resulted in a massive leak of gas followed by catastrophic explosions. The leaking source was verified by calculating the amount of released LPG and by analyzing captured photos recorded by the television news service. Two BLEVEs were also studied.