Related Experiment Video
Updated: Aug 4, 2026

Electrochemically and Bioelectrochemically Induced Ammonium Recovery
Published on: January 22, 2015
Improvement of ammonia removal in activated sludge process with feedforward-feedback aeration controllers
Darko Vrecko1, Nadja Hvala, Aljaz Stare
1Jozef Stefan Institute, Jamova 39, SI-1000 Ljubljana, Slovenia. darko.vrecko@ijs.si
Abstract:
In the paper three linear aeration controllers that can be easily implemented are presented and evaluated on the activated sludge process pilot plant. Controllers differ according to the information that is used about the process, which can be oxygen in the last aerobic reactor, ammonia in the last aerobic reactor and ammonia in the influent. The aeration controllers that are addressed are: oxygen cascade PI controller, ammonia cascade PI controller and ammonia feedforward-cascade PI controller. Experiments show that, in comparison with the oxygen cascade PI controller, the ammonia cascade PI controller allows better control of effluent ammonia and airflow savings of around 23%, while the ammonia feedforward-cascade PI controller gives the best reduction of ammonia peaks and can save up to 45% of the airflow.