Sick building syndrome in relation to air exchange rate, CO(2), room temperature and relative air humidity in
1Department of Medical Sciences, Occupational and Environmental Medicine, Uppsala University, University Hospital, Uppsala, Sweden. dan.norback@medsci.uu.se
Objective:
To study the effects of ventilation and temperature changes in computer classrooms on symptoms in students.
Methods:
Technical university students participated in a blinded study. Two classrooms had higher air exchange (4.1-5.2 ac/h); two others had lower (2.3-2.6 ac/h) air exchange. After 1 week, ventilation conditions were interchanged between the rooms. The students reported symptoms during the last hour, on a seven-step rating scale. Room temperature, relative air humidity (RH) carbon dioxide (CO(2)), PM10 and ultra-fine particles (UFP) were measured simultaneously (1 h). Illumination, air velocity, operative temperature, supply air temperature, formaldehyde, NO(2) and O(3) were measured. Multiple logistic regression was applied in cross-sectional analysis of the first answer (N = 355). Those participating twice (N = 121) were analysed longitudinally.
Results:
Totally 31% were females, 2.9% smokers and 3.8% had asthma. Mean CO(2) was 993 ppm (674-1,450 ppm), temperature 22.7 degrees C (20-25 degrees C) and RH 24% (19-35%). Lower and higher air exchange rates corresponded to a personal outdoor airflow of 7 l/s*p and 10-13 L/s*P, respectively. Mean PM10 was 20 microg/m(3) at lower and 15 microg/m(3) at higher ventilation flow. Ocular, nasal and throat symptoms, breathlessness, headache and tiredness were significantly more common at higher CO(2) and temperature. After mutual adjustment, ocular (OR = 1.52 per 1 degrees C), nasal (OR = 1.62 per 1 degrees C) and throat symptoms (OR = 1.53 per 1 degrees C), headache (OR = 1.51 per 1 degrees C) and tiredness (OR = 1.54 per 1 degrees C) were significantly associated with temperature; headache was associated only with CO(2) (OR = 1.19 per 100 ppm CO(2)). Longitudinal analysis demonstrated that increased room temperature was related to tiredness (P < 0.05).
Conclusion:
Computer classrooms may have CO(2) above 1,000 ppm and temperatures above 22 degrees C. Increased temperature and CO(2) may affect mucosal membrane symptoms, headaches and tiredness. Room temperature was most important. CO(2) associations may partly be temperature effects.
More Related Videos
Related Concept Videos
Assessment of Ventilation I: Respiratory Rate
A Ventilation assessment is critical for monitoring a patient's health status. Respiration, one of the most accessible vital signs, provides insights into the function of numerous body systems and can indicate serious health issues, such as brainstem injuries from head trauma.
Critical Guidelines for Assessing Ventilation:
Chronic Obstructive Pulmonary Disease-IV: Assessement and Diagnostic Studies
Medical History
Other Factors Affecting Respiration Centers
However, the ability to hold one's breath voluntarily is not limitless. When the CO2 concentration in the blood reaches a critical level,...
Factors Affecting Pulmonary Ventilation
Alveolar Surface Tension
The alveolar fluid lines the luminal surface of the alveoli and exerts a force called surface tension. This force is caused by the polar water molecules in the liquid being more strongly attracted to each...
Factors Affecting Body Temperature
Factors may include: