Various adsorbents for a solid phase extraction (SPE) method were used to study their ability to separate PCBs from transformer oil to rapidly determine their sub-ppm concentration in the transformer oil. Approximately 90% of the transformer oil could be removed from the PCBs by using a hydrophilic-lipophilic balanced copolymer (HLB) adsorbent, but the recovery of deca-chlorobiphenyl (deca-CB) used as a surrogate was only 24.5% due to lose during this cleanup process. The use of a silica adsorbent gave good results with 89.9% recovery of the deca-CB. The recovery of Aroclor 1242 and 1260 were 95.4 and 90.3% on silica, and 98.9 and 83.5% on HLB, respectively. Acid treatment was an essential step in removing the ambiguous interference peaks to help identify the PCBs. A decreased sensitivity of the electron capture detection (ECD) for PCBs was observed due to the presence of the remaining trace oil after the workup procedure. This loss in sensitivity was allowed for by using tetrachloroxylene as an internal standard, and this was found to be reliable for the criteria of quality control by employing an experiment in which LCS was spiked with 2mg/l of Aroclor 1260 and analyzed each day over a 25 day period. The MDL for the analytical method established in this study is 0.05 mg/l.
More Related Videos
Related Concept Videos
Extraction: Advanced Methods
Analyte Adsorption and Distribution
Voltammetry: Stripping Methods
Anodic Stripping Voltammetry (ASV)
ASV is used to determine metals and metalloids at trace levels. It involves two steps: deposition and stripping. First, a negative potential is applied to the...
Chromatography: Introduction
The phase in which the compounds linger or on which the compounds adsorb is called the stationary phase, whereas the mobile phase is the solvent that carries the solutes to be analyzed. In traditional column chromatography, the mixture flows through the stationary phase, and the compounds partition between the stationary and mobile phases...
Ion-Exchange Chromatography