Prevalence study of Legionella spp. contamination in Greek hospitals
Athena Mavridou1, Eleni Smeti, Georgia Mandilara
1Technological Educational Institution of Athens Athens, Greece. amavridou@teiath.gr
Abstract:
Water and swab samples were collected from 13 hospitals and analyzed for Legionella counts. Legionella was detected in eight out of 13 hospitals and in 22 of 130 water and swab-collected samples. A total of 72.7% of the strains were L. pneumophila ser. 1, 22.7% were L. pneumophila ser. 2-14, and 4.5% did not belong to any of these groups. AFLP typing of the L. pneumophila ser. 1 strains generated two distinguishable AFLP types. There was no significant correlation to the sample type with Legionella recovery. Legionella isolation was more likely to occur in the cooling towers than the water system. Water temperatures of 30-40 degrees C seem to favor Legionella growth. Of the 265 serum samples taken from the medical and technical staff for the control of IgG titre, 89.4% were negative, 7.2% were positive, and for 3.4% the result was doubtful. No association between IgG titre and maximum observed level of Legionella occurrence was detected.
Insights
Legionella bacteria were found in hospital water systems, particularly cooling towers, with L. pneumophila ser. 1 being the most common type. No link was found between staff IgG titres and Legionella presence.
Area of Science:
- Environmental microbiology
- Hospital-acquired infections
Background:
- Legionella is a bacterium that can cause Legionnaires' disease, a severe form of pneumonia.
- Hospitals are environments where Legionella can proliferate in water systems, posing a risk to patients.
Purpose of the Study:
- To investigate the prevalence and characteristics of Legionella in hospital water systems.
- To identify potential sources and environmental factors favoring Legionella growth.
- To assess the association between staff immune response and environmental Legionella levels.
Main Methods:
- Water and swab samples were collected from 13 hospitals.
- Samples were analyzed for Legionella counts and serotypes.
- AFLP typing was used for L. pneumophila ser. 1 strains.
- Serum samples from staff were tested for IgG titres.
Main Results:
- Legionella was detected in 8 out of 13 hospitals and 22 out of 130 samples.
- L. pneumophila ser. 1 was the predominant serotype (72.7%).
- Cooling towers were more likely to harbor Legionella than other water systems.
- Water temperatures between 30-40°C favored Legionella growth.
- No significant correlation was found between sample type and Legionella recovery.
- AFLP typing identified two main types of L. pneumophila ser. 1.
- 89.4% of staff serum samples were negative for IgG antibodies, with 7.2% positive and 3.4% doubtful.
- No association was detected between staff IgG titres and environmental Legionella levels.
Conclusions:
- Legionella is prevalent in hospital water systems, with cooling towers being a significant reservoir.
- Environmental factors like temperature play a role in Legionella proliferation.
- Current staff IgG titres do not appear to be directly associated with the observed levels of Legionella in the hospital environment.