Related Experiment Video
Updated: Jul 2, 2026

Measuring Sub-23 Nanometer Real Driving Particle Number Emissions Using the Portable DownToTen Sampling System
Published on: May 22, 2020
Desiccant wheels as gas-phase absorption (GPA) air cleaners: evaluation by PTR-MS and sensory assessment
1International Centre for Indoor Environment and Energy, Department of Civil Engineering, Technical University of Denmark, Lyngby, Denmark. fl@byg.dtu.dk
Unlabelled:
Two experiments were conducted to investigate the use of the co-sorption effect of a desiccant wheel for improving indoor air quality. One experiment was conducted in a climate chamber to investigate the co-sorption effect of a desiccant wheel on the chemical removal of indoor air pollutants; another experiment was conducted in an office room to investigate the resulting effect on perceived air quality. A dehumidifier with a silica-gel desiccant wheel was installed in the ventilation system of the test chamber and office room to treat the recirculation airflow. Human subjects, flooring materials and four pure chemicals (formaldehyde, ethanol, toluene and 1,2-dichloroethane) were used as air pollution sources. Proton-Transfer-Reaction--Mass Spectrometry (PTR-MS) and sensory subjects were used to characterize the effectiveness of chemical and sensory pollution removal of the desiccant wheel. The experiments revealed that all the measured VOCs were removed effectively by the desiccant wheel with an average efficiency of 94% or higher; more than 80% of the sensory pollution load was removed and the percentage dissatisfied with the air quality decreased from 70% to 20%. These results indicate that incorporating a regenerative desiccant wheel in a ventilation system is an efficient way of removing indoor VOCs.
Practical Implications:
This study may lead to the development of new air cleaners and validates a new concept for the design of ventilation systems that can improve indoor air quality and reduce energy consumption.
Related Concept Videos
Gas Chromatography: Types of Detectors-II
Gas Chromatography–Mass Spectrometry (GC–MS)
A gas chromatograph consists of a long, narrow capillary column with a polysiloxane coating on the inner wall. The coating...
Gas Chromatography: Types of Detectors-I
TCD is the earliest and most widely used detector that operates by measuring the changes in the thermal conductivity of the carrier gas. When a sample compound enters the detector,...
Gas Chromatography: Overview of Detectors
A non-destructive detector allows a sample to be analyzed without altering or consuming it, meaning the sample can be collected after detection for further analysis. Examples include thermal conductivity detectors and...
Gas Chromatography: Introduction
In GC, a sample is vaporized and mixed with an inert carrier gas (the mobile phase), which transports it through a column.