Related Experiment Video
Updated: Jun 28, 2026

Fluorescent Paper Strips for the Detection of Diesel Adulteration with Smartphone Read-out
Published on: November 9, 2018
Synchronous fluorescence and excitation emission characteristics of transformer oil ageing
Subbiah Deepa1, R Sarathi, Ashok K Mishra
1Department of Chemistry, Indian Institute of Technology Madras, Chennai 600 036, India.
Abstract:
This paper describes the evaluation of synchronous fluorescence spectroscopy (SFS) and excitation emission matrix fluorescence (EEMF) spectroscopy as means of monitoring transformer oil degradation. When accelerated thermal ageing method is used, the onset of degradation of transformer oil on 17th day and transformer oil with polypropylene and cellulosic paper on 23rd and 27th days is sensitively reflected in the SFS and EEMF fluorescence spectral characteristics.
Related Concept Videos
Variables Affecting Phosphorescence and Fluorescence
Fluorescence and Phosphorescence: Instrumentation
Energy Losses in Transformers
There are four main reasons for energy losses in transformers.
The first cause can be the high resistance of the copper windings...