Contamination of fresh air intakes due to downwash from a rooftop structure
Pat Saathoff1, Amit Gupta, Ted Stathopoulos
1Centre for Building Studies, Concordia University, Montréal, Québec, Canada.
Abstract:
The effect of rooftop structures on the dispersion of building exhaust was evaluated using wind tunnel experiments with an isolated building for four different full-scale equivalent heights varying from 15 to 70 m. The stack was located on the roof of the building downwind of the rooftop structure. In some cases, downwash produced by the rooftop structure caused a significant reduction in dilution (i.e., increased contaminant concentration) compared with results obtained with a flat-roofed model. For the wind normal to the building, the effect of the rooftop structure depended on building height and the crosswind width of the structure. Maximum reduction in dilution occurred for the 15-m building with a wide penthouse. The influence of the rooftop structure on plume behavior for the normal wind diminished as building height increased because of an increase in size of the separated flow region above the roof. On the other hand, for an oblique wind at 45 degrees, the rooftop structure produced low dilution for all building heights. The paper shows that the American Society of Heating, Refrigerating and Air-Conditioning Engineers geometric stack design method and dilution model can lead to an unconservative design.
Related Concept Videos
Oxygen Delivering System II: Venturi Mask and Transtracheal Oxygen
Venturi Mask
The Venturi mask, named after the Venturi effect, is designed to deliver precise oxygen concentrations. It consists of a large tube with an oxygen inlet that narrows down, causing a pressure drop that pulls air in through adjustable side ports. The mask is a lightweight,...
Design Example: Calculating Safe Diameter for Wind-Exposed Disc
Design Example: Sustainability in Concrete Building
There are multiple approaches to achieve sustainability in a commercial concrete building. For instance, construct a concrete parking area under the building, utilizing pervious concrete paver blocks in open areas to facilitate rainwater collection through an underground cistern.
Transmission-based Precautions II: Airborne and Protective Environment
Airborne precautions:
Use airborne precautions when treating patients known or suspected to have diseases that spread through the air—for example, tuberculosis or measles. These organisms are present in smaller droplets expelled by an infected person and...
Effects of Air-entrainment in Concrete
Cavity Drainage and Flashings in Masonry walls
Weep holes, strategically placed at the base of the cavity, are critical for draining accumulated water. These openings are created by leaving head...