Control of Legionella contamination in a hospital water distribution system by monochloramine
Isabella Marchesi1, Stefano Cencetti, Patrizia Marchegiano
1Department of Public Health Sciences, University of Modena and Reggio Emilia, Italy.
Background:
We report the results of 1-year application of monochloramine to control Legionella pneumophila contamination in a hospital hot water distribution system.
Methods:
In the main building of the hospital, a device continuously distributing monochloramine was installed. Legionella pneumophila and Pseudomonas spp contamination was followed in comparison with 2 other water networks in the same building using chlorine dioxide.
Results:
Monochloramine significantly reduced the number of contaminated sites compared with baseline (from 97.0% to 13.3%, respectively), chlorine dioxide device I (from 100% to 56.7%, respectively), and device II (from 100% to 60.8%, respectively). No positive sample exceeded 10(4) colony-forming units/L versus 59.4% at baseline.
Conclusion:
Monochloramine could represent a good alternative to chlorine dioxide in controlling legionellae contamination in public and private buildings.
Insights
Monochloramine effectively controlled Legionella pneumophila in hospital water systems over one year. This disinfectant significantly reduced contamination compared to baseline and chlorine dioxide, offering a promising alternative for building water safety.
Area of Science:
- Environmental Microbiology
- Water Treatment Technologies
- Hospital Infection Control
Background:
- Legionella pneumophila poses a significant risk in hospital water systems.
- Controlling Legionella pneumophila contamination is crucial for patient safety.
- Existing disinfection methods may have limitations.
Purpose of the Study:
- To evaluate the efficacy of monochloramine for controlling Legionella pneumophila.
- To compare monochloramine disinfection with chlorine dioxide in a hospital setting.
- To assess the long-term impact of monochloramine on water system contamination.
Main Methods:
- Continuous monochloramine distribution in a hospital hot water system.
- Monitoring Legionella pneumophila and Pseudomonas spp. contamination.
- Comparative analysis with chlorine dioxide in parallel water networks.
Main Results:
- Monochloramine reduced contaminated sites from 97.0% to 13.3%.
- Significant reduction observed compared to baseline and chlorine dioxide (56.7% and 60.8%).
- No positive samples exceeded 10(4) CFU/L post-treatment, a marked improvement from baseline (59.4%).
Conclusions:
- Monochloramine is a highly effective disinfectant for Legionella pneumophila.
- It presents a viable and potentially superior alternative to chlorine dioxide.
- Recommended for controlling legionellae in diverse building water systems.
Related Concept Videos
Physical Methods for Controlling Microbial Growth: Radiation and Filtration
Methods for Controlling Microbial Growth
Waterproofing and Anti-Bacterial Admixtures in Concrete
Waterproofing admixtures render concrete hydrophobic,...
Healthcare Associated Infections II: Preventive Measures
The best practices for preventing healthcare-associated infections include hand hygiene, patient risk...
Biological Methods for Microbial Control