Related Experiment Video
Updated: May 6, 2026

Determining Viral Disinfection Efficacy of Hot Water Laundering
Published on: June 21, 2022
Role of Hot Water System Design on Factors Influential to Pathogen Regrowth: Temperature, Chlorine Residual, Hydrogen
Randi H Brazeau1, Marc A Edwards
1Department of Earth and Atmospheric Sciences, Metropolitan State University of Denver , Denver, Colorado.
Abstract:
Residential water heating is linked to growth of pathogens in premise plumbing, which is the primary source of waterborne disease in the United States. Temperature and disinfectant residual are critical factors controlling increased concentration of pathogens, but understanding of how each factor varies in different water heater configurations is lacking. A direct comparative study of electric water heater systems was conducted to evaluate temporal variations in temperature and water quality parameters including dissolved oxygen levels, hydrogen evolution, total and soluble metal concentrations, and disinfectant decay. Recirculation tanks had much greater volumes of water at temperature ranges with potential for increased pathogen growth when set at 49°C compared with standard tank systems without recirculation. In contrast, when set at the higher end of acceptable ranges (i.e., 60°C), this relationship was reversed and recirculation systems had less volume of water at risk for pathogen growth compared with conventional systems. Recirculation tanks also tended to have much lower levels of disinfectant residual (standard systems had 40-600% higher residual), 4-6 times as much hydrogen, and 3-20 times more sediment compared with standard tanks without recirculation. On demand tankless systems had very small volumes of water at risk and relatively high levels of disinfectant residual. Recirculation systems may have distinct advantages in controlling pathogens via thermal disinfection if set at 60°C, but these systems have lower levels of disinfectant residual and greater volumes at risk if set at lower temperatures.
Related Concept Videos
Methods of Sterilization I: Physical Methods
Steam sterilization uses non-toxic, low-cost moist heat in the form of saturated steam under pressure, which is fast, microbicidal, and sporicidal, and quickly warms and penetrates fabrics. Autoclaves, or steam sterilizers, expose each item to direct steam contact for a predetermined time at the necessary...
Physical Methods for Controlling Microbial Growth: Temperature
Methods of Sterilization II: Chemical Methods
Using chemical sterilization rather than heat to clean out equipment is recommended. It eradicates and removes all bacteria,...
Factors Influencing Microbial Growth: Temperature
Physical Methods for Controlling Microbial Growth: Radiation and Filtration
Factors Influencing Microbial Growth: Osmolarity