Related Experiment Video
Updated: May 5, 2026

Remote Laboratory Management: Respiratory Virus Diagnostics
Published on: April 6, 2019
Fumigation of a laboratory-scale HVAC system with hydrogen peroxide for decontamination following a biological
K M Meyer1, M W Calfee, J P Wood
1Oak Ridge Institute for Science and Education, Research Triangle Park, NC, USA; US EPA, Office of Research and Development, National Homeland Security Research Center, Research Triangle Park, NC, USA.
Aims:
To evaluate hydrogen peroxide vapour (H2 O2 ) for its ability to inactivate Bacillus spores within a laboratory-scale heating, ventilation and air-conditioning (HVAC) duct system.
Methods And Results:
Experiments were conducted in a closed-loop duct system, constructed of either internally lined or unlined galvanized metal. Bacterial spores were aerosol-deposited onto 18-mm-diameter test material coupons and strategically placed at several locations within the duct environment. Various concentrations of H2 O2 and exposure times were evaluated to determine the sporicidal efficacy and minimum exposure needed for decontamination. For the unlined duct, high variability was observed in the recovery of spores between sample locations, likely due to complex, unpredictable flow patterns within the ducts. In comparison, the lined duct exhibited a significant desorption of the H2 O2 following the fumigant dwell period and thus resulted in complete decontamination at all sampling locations.
Conclusions:
These findings suggest that decontamination of Bacillus spore-contaminated unlined HVAC ducts by hydrogen peroxide fumigation may require more stringent conditions (higher concentrations, longer dwell duration) than internally insulated ductwork.
Significance And Impact Of The Study:
These data may help emergency responders when developing remediation plans during building decontamination.
Related Concept Videos
Methods of Sterilization II: Chemical Methods
Using chemical sterilization rather than heat to clean out equipment is recommended. It eradicates and removes all bacteria,...
Transmission-based Precautions II: Airborne and Protective Environment
Airborne precautions:
Use airborne precautions when treating patients known or suspected to have diseases that spread through the air—for example, tuberculosis or measles. These organisms are present in smaller droplets expelled by an infected person and...
Physical Methods for Controlling Microbial Growth: Radiation and Filtration
Cleaning, Sterilization, and Disinfection
Cleaning
The cleaning process usually involves using water with detergents or enzymatic cleaner and removing foreign material from objects and surfaces, including organic material such as body fluids or inorganic material like soil. Cleaning is performed before high-level disinfection and sterilization because foreign materials on the cover of the devices interfere with process...
Methods of Sterilization I: Physical Methods
Steam sterilization uses non-toxic, low-cost moist heat in the form of saturated steam under pressure, which is fast, microbicidal, and sporicidal, and quickly warms and penetrates fabrics. Autoclaves, or steam sterilizers, expose each item to direct steam contact for a predetermined time at the necessary...
Microbial Bioremediation of Pesticides