Study of cross-shaped ultrasonic array sensor applied to partial discharge location in transformer oil
Jisheng Li1, Xiaohu Xin, Yongfen Luo
1School of Electrical Engineering, Xi'an Jiaotong University, Xi'an Shanxi 710049, China.
Abstract:
A conformal combined sensor is designed and it is used in Partial Discharge (PD) location experiments in transformer oil. The sensor includes a cross-shaped ultrasonic phased array of 13 elements and an ultra-high-frequency (UHF) electromagnetic rectangle array of 2 × 2 elements. Virtual expansion with high order cumulants, the ultrasonic array can achieve the effect of array with 61 elements. This greatly improves the aperture and direction sharpness of original array and reduces the cost of follow-up hardware. With the cross-shaped ultrasonic array, the results of PD location experiments are precise and the maximum error of the direction of arrival (DOA) is less than 5°.
Related Concept Videos
Three-Phase Short Circuit—Unloaded Synchronous Machine
This behavior occurs due to the magnetic flux produced by the short-circuit armature currents. Initially, these currents follow high-reluctance paths but eventually shift to...
Power System Three-Phase Short Circuits
Instrument Transformers
Transformers in Distribution System
Distribution substation transformers come in various ratings and typically use mineral oil for insulation and cooling. To prevent moisture and air from entering the oil, some transformers use an inert gas like nitrogen to fill the...
Energy Losses in Transformers
There are four main reasons for energy losses in transformers.
The first cause can be the high resistance of the...
Equivalent Circuits for Practical Transformers
In a practical transformer, each winding exhibits resistance and leakage reactance. The...