Related Experiment Video
Updated: May 4, 2026

Design and Optimization Strategies of a High-Performance Vented Box
Published on: June 9, 2023
Pressure losses across multiple fittings in ventilation ducts
1Department of Building Services Engineering, The Hong Kong Polytechnic University, Hong Kong.
Abstract:
The accurate prediction of pressure losses across in-duct fittings is of significance in relation to the accurate sizing and good energy efficiency of air-delivery systems. Current design guides provide design methods and data for the prediction of pressure losses only for a single and isolated fitting. This study presents an investigation of pressure losses across multiple interactive in-duct fittings in a ventilation duct. A laboratory measurement of pressure losses across one fitting and multiple fittings in a ventilation duct is carried out. The pressure loss across multiple interactive fittings is lower than that across multiple similar individual fittings, while the percentage decrease is dependent on the configuration and combination of the fittings. This implies that the pressure loss across multiple closely mounted fittings calculated by summing the pressure losses across individual fittings, as provided in the ASHRAE handbook and the CIBSE guide, is overpredicted. The numerical prediction of the pressure losses across multiple fittings using the large-eddy simulation (LES) model shows good agreement with the measured data, suggesting that this model is a useful tool in ductwork design and can help to save experimental resources and improve experimental accuracy and reliability.
Related Concept Videos
Minor Losses in Pipes
Valves play a significant role in generating minor losses by obstructing or redirecting the fluid flow. When a valve is closed or partially closed, it restricts the flow...
Design Example: Designing a Residential Plumbing System
Major Losses in Pipes
Fluid flow can be classified as laminar or turbulent, primarily based on the Reynolds number. This dimensionless number reflects the relative influence of inertial to...
Multiple Pipe Systems
Series Configuration
In a series configuration, fluid flows sequentially from one pipe...
Single Pipe Systems
In a Type I problem, fluid properties (density and viscosity), pipe characteristics (including diameter, length, and surface roughness), and the flow rate or average velocity are...
Bernoulli's Equation: Problem Solving
The first step is to compute the cross-sectional areas of the pipe and the Venturi throat to analyze the pressure difference indicated by the pressure gauge. Next, the continuity equation is...