Related Experiment Video
Updated: May 1, 2026

Coupling Carbon Capture from a Power Plant with Semi-automated Open Raceway Ponds for Microalgae Cultivation
Published on: August 14, 2020
Improving aeration control at the Ljubljana wastewater treatment plant
D Vrečko1, U Zupančič2, R Babič3
1Jožef Stefan Institute, Jamova 39, 1000 Ljubljana, Slovenia
Abstract:
This paper describes an improvement to the aeration control at the Ljubljana wastewater treatment plant. Several changes were made to the existing aeration control. An adjustment to the parameters of the common air pressure controller contributes to a more responsive operation of the compressors. The introduction of the air pressure set-point controller adjusts the air pressure in the common air rail according to the changes in the plant load. The introduction of the airflow controllers reduces the variation in the oxygen concentrations in the aerobic reactors and, consequently, enables a reduction in the oxygen set-points. With the improved aeration control, savings of up to 10% in the electricity used for aeration are achieved on a yearly basis.
Related Concept Videos
Bioreactor Controls-II
Bioreactor Controls-I
Bioreactor Design and Operational System
Bioreactor Controls-III
Designing Growth Media for Bioreactors
Bioremediation