Does a mobile laminar airflow screen reduce bacterial contamination in the operating room? A numerical study using
Sasan Sadrizadeh1, Ann Tammelin2, Peter V Nielsen3
1Division of Fluid and Climate Technology, School of Architecture and the Built Environment, KTH Royal Institute of Technology, Stockholm, Sweden.
Adding mobile laminar airflow (MLAF) units to operating room (OR) ventilation significantly reduces airborne bacteria, crucial for preventing surgical site infections in orthopedic implant surgery. The MLAF
Area of Science:
- Healthcare Engineering
- Microbiology
- Surgical Safety
Background:
- Airborne bacteria in operating rooms (ORs) pose a risk of surgical wound contamination.
- Efficient ventilation systems are key to reducing air contamination during surgery.
- This study investigates the impact of mobile laminar airflow (MLAF) units on OR air quality.
Purpose of the Study:
- To assess the additive effect of MLAF units on microbiological air quality in an OR with existing turbulent-mixing ventilation.
- To determine if MLAF units can reduce bacterial contamination to acceptable levels for orthopedic implant surgery.
Main Methods:
- Utilized a recently designed OR as a physical model for simulation.
- Employed computational fluid dynamics (CFD) for numerical calculations.
- Simulated bacterial air contamination and sedimentation rates with and without MLAF units.
Main Results:
- Mobile laminar airflow units significantly reduced airborne and sedimenting bacteria-carrying particles.
- Contamination levels reached acceptable standards for orthopedic implant surgery when MLAF was used.
- No significant changes in sedimentation rates were observed in the OR periphery.
Conclusions:
- MLAF units are a viable option for enhancing OR air quality when primary ventilation is insufficient for orthopedic implant surgery.
- The effectiveness of MLAF is localized, with a significant impact within approximately 1 meter of the unit.
- Increasing MLAF air velocity beyond 0.4 m/s does not expand its effective range.