Evaluation of 3 dental unit waterline contamination testing methods
General Dentistry
|January 10, 2015
Summary
Comparing heterotrophic plate count (HPC) methods for dental unit waterlines (DUWLs), this study found Standard Method 9215C most accurate. The chairside method is useful, but 9215E is unsuitable for DUWL monitoring.
Area of Science:
- Microbiology
- Dental Public Health
Background:
- Dental unit waterlines (DUWLs) can harbor heterotrophic bacteria, posing potential risks.
- Previous studies show inconsistent results when measuring bacterial counts in DUWL samples.
Purpose of the Study:
- To compare the accuracy of an in-office chairside method with two commercial laboratory methods (Standard Methods 9215C and 9215E) for heterotrophic plate count (HPC) bacteria in DUWL samples.
Main Methods:
- Sixty-three DUWL samples were analyzed.
- Results from a chairside method were compared against Standard Method 9215C and 9215E.
Main Results:
- Standard Method 9215E yielded limited detection of heterotrophic organisms at 35°C, indicating unsuitability for DUWL monitoring.
- The in-office chairside method demonstrated utility for DUWL quality monitoring.
- Standard Method 9215C provided the most accurate results for HPC bacteria in DUWL samples.
Conclusions:
- Standard Method 9215C is the most accurate method for HPC bacteria enumeration in DUWLs.
- While the chairside method is practical for DUWL monitoring, Standard Method 9215E is not recommended.
More Related Videos
11:19Preparation and Testing of Impedance-based Fluidic Biochips with RTgill-W1 Cells for Rapid Evaluation of Drinking Water Samples for Toxicity
Published on: March 7, 2016
9.5K
09:02A Method to Test the Efficacy of Handwashing for the Removal of Emerging Infectious Pathogens
Published on: June 7, 2017
20.0K
Related Concept Videos
Testing Water Quality
595
When the quality of water for concrete preparation is uncertain, its impact on the setting time of cement and compressive strength of mortar is assessed by comparison with de-ionized or distilled water benchmarks. American Society for Testing and Materials (ASTM) C1602 requires the setting times to be within 90 minutes of the control, British Standard (BS) 3146:1980 allows a 30-minute variance in the initial setting, while British Standards European Norm (BS EN) 1008 specifies initial setting...
595
Quality of Water
724
In concrete preparation, the quality of water is paramount as it affects the strength and durability of the concrete. Potable water is usually preferred; however, it must not have excessive sodium or potassium to prevent compromising the concrete's integrity. Water quality is typically evaluated based on impurities such as dissolved solids, chlorides, and sulfates, and its pH value is ideally between 6 and 8. Even slightly acidic natural water may be acceptable unless it contains harmful...
724