Fault-induced delayed voltage recovery in a long inhomogeneous power-distribution feeder
Irina Stolbova1, Scott Backhaus2,3, Michael Chertkov3,4
1Moscow Institute of Physics and Technology, Dolgoprudnyj, Moscow Regiona 141700, Russia.
Abstract:
We analyze the dynamics of a distribution circuit loaded with many induction motors and subjected to sudden changes in voltage at the beginning of the circuit. As opposed to earlier work by Duclut et al. [Phys. Rev. E 87, 062802 (2013)], the motors are disordered, i.e., the mechanical torque applied to the motors varies in a random manner along the circuit. In spite of the disorder, many of the qualitative features of a homogeneous circuit persist, e.g., long-range motor-motor interactions mediated by circuit voltage and electrical power flows result in coexistence of the spatially extended and propagating normal and stalled phases. We also observed a new phenomenon absent in the case without inhomogeneity or disorder. Specifically, the transition front between the normal and stalled phases becomes somewhat random, even when the front is moving very slowly or is even stationary. Motors within the blurred domain appear in a normal or stalled state depending on the local configuration of the disorder. We quantify the effects of the disorder and discuss the statistics of distribution dynamics, e.g., the front position and width, total active and reactive consumption of the feeder, and maximum clearing time.
Related Concept Videos
Reclosers and Fuses
A comprehensive protection scheme for radial distribution...
Primary Distribution
Power System Three-Phase Short Circuits
Three-Phase Short Circuit—Unloaded Synchronous Machine
This behavior occurs due to the magnetic flux produced by the short-circuit armature currents. Initially, these currents follow high-reluctance paths but eventually shift to...
Radial System Protection
In a radial system with a fault downstream of the third breaker, ideally, only the third breaker will open, isolating the fault and interrupting the load connected beyond it. The second breaker has a longer delay setting,...
Bus Impedance Matrix
In the first circuit, all machine voltage sources are short-circuited, leaving only the prefault voltage source at the fault location. The positive-sequence bus impedance matrix can be determined by solving the nodal equations,...