Related Experiment Video
Updated: Apr 11, 2026

Use of Galleria mellonella as a Model Organism to Study Legionella pneumophila Infection
Published on: November 22, 2013
Trend of Legionella colonization in hospital water supply
D D'Alessandro1, M Fabiani2, F Cerquetani3
1Department of Architecture and Planning, Sapienza University of Rome, Italy.
Background:
In many nosocomial Legionella outbreaks water distribution systems are the most frequent source of infection.
Objectives:
Considering the hospital waterline old age, an investigation on colonization by Legionella spp was carried out in order to evaluate the pipeline system weaknesses and to implement environmental preventive measures.
Methods:
From 2004 to 2010, overall 97 samples from the water line were collected. The samples were analyzed according to the italian Legionella spp standard methods; water temperature, pH and residual free chlorine were determined at the time of collection. X2 test, exact-test and t-test were used to compare proportions and means.
Results:
Overall 28 samples (23.7%) were positive for Legionella spp, and five of them (17.9%) exceeded the threshold level >104 cfu/L. The number of positive samples varied along the years, showing a significant increasing trend (X2 for trend = 11.5; p<0.01), but most occurred in 2008 (53,6%), when the hospital underwent major building reconstruction. Samples positive for Legionella spp by comparison to negative ones showed a lower free chlorine concentration (0.08 mg/L vs 0.15 mg/L) and a higher water temperature (46.1° vs 42.7°). Actually the percentage of positive samples decreased significantly with the increasing in free chlorine in the water (X2 for trend = 8.53; p<0.01). The samples collected at the connection between public water line with the hospital supply network were always free from Legionella. All hospital buildings were colonized by Legionella spp, although 80% of samples >104 cfu/L occurred in the C-building. No cases of nosocomial legionellosis were reported during the study period.
Conclusions:
Hospital water system showed a diffuse colonization by Legionella spp, although the degree of contamination reached the threshold level (>104 cfu/L) only in a small percentage of samples, showing a substantial effectiveness of the control measures applied.
Related Concept Videos
Reservoir of Infection
Cholera
Atypical Pneumonia
Healthcare Associated Infections II: Preventive Measures
The best practices for preventing healthcare-associated infections include hand hygiene, patient risk...
Healthcare Associated Infections I: Iatrogenic, Exogenic and Endogenic
HAIs significantly increase the cost of health care. Extended stays in healthcare institutions, increased disability, increased costs of medications, including specialized antibiotics, and prolonged recovery times add to the patient's expenses and the healthcare institution and funding bodies.
Quality of Water