Application of polynomial control to design a robust oscillation-damping controller in a multimachine power system
Related Experiment Video
Updated: Apr 3, 2026

Experimental Investigation of the Hierarchical Control in DC Microgrids Using a Real-time Simulator
Published on: February 14, 2025
Hamed Hasanvand1, Babak Mozafari1, Mohammad R Arvan2
1Department of Electrical Engineering, Science and Research Branch, Islamic Azad University, Tehran, Iran.
Abstract:
This paper addresses the application of a static Var compensator (SVC) to improve the damping of interarea oscillations. Optimal location and size of SVC are defined using bifurcation and modal analysis to satisfy its primary application. Furthermore, the best-input signal for damping controller is selected using Hankel singular values and right half plane-zeros. The proposed approach is aimed to design a robust PI controller based on interval plants and Kharitonov's theorem. The objective here is to determine the stability region to attain robust stability, the desired phase margin, gain margin, and bandwidth. The intersection of the resulting stability regions yields the set of kp-ki parameters. In addition, optimal multiobjective design of PI controller using particle swarm optimization (PSO) algorithm is presented. The effectiveness of the suggested controllers in damping of local and interarea oscillation modes of a multimachine power system, over a wide range of loading conditions and system configurations, is confirmed through eigenvalue analysis and nonlinear time domain simulation.
Related Concept Videos
Multimachine Stability
In analyzing the system, the nodal equations represent the relationship between bus voltages, machine voltages, and machine currents. The nodal equation is given by:
Time-Domain Interpretation of PD Control
Consider the example of control of motor torque. Initially, a positive...
Time and frequency -Domain Interpretation of PI Control
Acting as a low-pass filter, the PI controller slows the system's response and extends settling times. This requires...
PD Controller: Design
Designing a continuous-data controller requires selecting and linking components like adders and integrators, which are fundamental in Proportional,...
Frequency-Domain Interpretation of PD Control
The proportional control gain, combined with the...
Second Order systems I
By reinterpreting the system, one can derive the closed-loop transfer function, which...