Budget-limited thermal biology: Design, construction and performance of a large, walk-in style temperature-controlled
Eloy Martinez1, Salvatore J Agosta2
1Center for Environmental Studies, Virginia Commonwealth University, Richmond, VA 23284, USA.
Abstract:
We describe a partial redesign of the conventional air-conditioning system and apply it to the construction of a relatively large (1.87m(3) air mass), walk-in style temperature-controlled chamber (TCC) using parts easily obtained in most countries. We conducted several tests to demonstrate the performance of the TCC. Across the physiologically relevant range of 5-37°C, the TCC took 26.5-50.0min to reach the desired set point temperature. Once at set point, temperature inside the chamber was controlled with an accuracy of ±1.0°C. User-entry effects on deviations from and return times to set point temperature were minimal. Overall, performance of the TCC was sufficient to make precise physiological measurements of insect metabolic rate while controlling assay temperature. Major advantages of the TCC include its simplicity, flexibility, and low cost.