Controlling Indoor Air Pollution from Moxibustion

Chung-Yen Lu1,2, Sy-Yuan Kang3, Shu-Hui Liu4,5

  • 1School of Post-Baccalaureate Chinese Medicine, China Medical University, Taichung 404, Taiwan. u100030082@cmu.edu.tw.

Insights

Moxibustion in hospitals can pollute indoor air. Using old moxa wool and local exhaust ventilation effectively reduces harmful pollutants, unlike air cleaners, improving hospital air quality.

Area of Science:

  • Environmental Health
  • Occupational Health
  • Traditional Chinese Medicine

Background:

  • Hospital indoor air quality (IAQ) is crucial for patient and staff health.
  • Moxibustion in Traditional Chinese Medicine (TCM) outpatient departments (OPDs) can generate indoor air pollution.
  • Previous studies indicate elevated pollutants during moxibustion in clinics.

Purpose of the Study:

  • To investigate indoor air pollutants during moxibustion in a hospital OPD.
  • To compare the effectiveness of different control strategies for moxibustion-related air pollution.

Main Methods:

  • Measured indoor carbon dioxide (CO₂), carbon monoxide (CO), formaldehyde (HCHO), total volatile organic compounds (TVOCs), PM10, and PM2.5.
  • Compared pollutant levels using alternative old moxa wools, local exhaust ventilation, and an air cleaner.

Main Results:

  • Burning old moxa wool significantly reduced gaseous pollutants (except aerosols) compared to fresh moxa wool.
  • Local exhaust ventilation effectively reduced most aerosols.
  • Air cleaners were inefficient, especially for gaseous pollutants.

Conclusions:

  • Combining old moxa wool and local exhaust ventilation is a suitable strategy for controlling indoor air pollution from moxibustion.
  • This approach can help maintain safer IAQ in hospital settings where moxibustion is practiced.