Evaluation of Low-Cost Mitigation Measures Implemented to Improve Air Quality in Nursery and Primary Schools
Juliana P Sá1, Pedro T B S Branco2, Maria C M Alvim-Ferraz3
1LEPABE-Laboratory for Process Engineering, Environment, Biotechnology and Energy, Faculty of Engineering, University of Porto, Rua Dr. Roberto Frias, 4200-465 Porto, Portugal. julianasa@fe.up.pt.
Insights
Low-cost measures improved indoor air quality in schools, significantly reducing carbon dioxide (CO₂). However, pollutant levels for PM2.5, PM10, and formaldehyde (CH₂O) often remained unsafe for children
Area of Science:
- Environmental Health
- Indoor Air Quality Research
- Pediatric Health
Background:
- Indoor air pollution poses significant health risks, particularly to children in educational settings.
- Children's prolonged indoor exposure in schools necessitates effective air quality management strategies.
- Existing indoor air quality (IAQ) standards and recommendations often serve as benchmarks for health protection.
Purpose of the Study:
- To evaluate the effectiveness of implemented low-cost mitigation measures in improving school indoor air quality.
- To assess changes in pollutant concentrations before and after the application of air quality interventions.
- To compare measured IAQ parameters against national legislation and World Health Organization (WHO) guidelines.
Main Methods:
- Conducted two indoor air quality monitoring campaigns in nursery and primary schools.
- Performed continuous measurements of various pollutants including CO₂, PM₂.₅, PM₁₀, CH₂O, VOCs, and radon.
- Measured temperature and relative humidity, comparing pre- and post-mitigation data.
Main Results:
- Exceedances of national and WHO limits were observed for PM₂.₅, PM₁₀, CO₂, and CH₂O in both campaigns.
- Temperature and relative humidity levels frequently surpassed ASHRAE recommended ranges.
- Post-mitigation measurements showed significant reductions in pollutant concentrations, especially for CO₂.
Conclusions:
- Low-cost mitigation measures demonstrated a positive impact on indoor air quality, particularly for CO₂.
- Despite improvements, the implemented measures were not consistently sufficient to ensure safe air quality levels.
- Further interventions may be necessary to fully protect children's health from indoor air pollution in schools.
Abstract:
Indoor air pollution mitigation measures are highly important due to the associated health impacts, especially on children, a risk group that spends significant time indoors. Thus, the main goal of the work here reported was the evaluation of mitigation measures implemented in nursery and primary schools to improve air quality. Continuous measurements of CO₂, CO, NO₂, O₃, CH₂O, total volatile organic compounds (VOC), PM₁, PM2.5, PM10, Total Suspended Particles (TSP) and radon, as well as temperature and relative humidity were performed in two campaigns, before and after the implementation of low-cost mitigation measures. Evaluation of those mitigation measures was performed through the comparison of the concentrations measured in both campaigns. Exceedances to the values set by the national legislation and World Health Organization (WHO) were found for PM2.5, PM10, CO₂ and CH₂O during both indoor air quality campaigns. Temperature and relative humidity values were also above the ranges recommended by American Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE). In general, pollutant concentrations measured after the implementation of low-cost mitigation measures were significantly lower, mainly for CO₂. However, mitigation measures were not always sufficient to decrease the pollutants' concentrations till values considered safe to protect human health.