Related Experiment Video
Updated: Feb 22, 2026

Purification of Pathogen Vacuoles from Legionella-infected Phagocytes
Published on: June 19, 2012
Industrial Cooling Tower Disinfection Treatment to Prevent Legionella spp
Matteo Iervolino1, Benedetta Mancini2, Sandra Cristino3
1Department of Biological, Geological and Environmental Sciences, BiGeA, University of Bologna, via San Giacomo 12, 40126 Bologna, Italy. matteo.iervolino2@unibo.it.
Abstract:
The contamination of industrial cooling towers has been identified as one cause of legionellosis, but the real risk has been underestimated. Two different disinfection treatments were tested on Legionella colonization in an industrial Cooling Tower System (CTS). Environmental monitoring of Legionella, P. aeruginosa, and a heterotrophic plate count (HPC) at 36 °C was performed from June to October 2016. The disinfection procedures adopted were based on hydrogen peroxide (H₂O₂) and silver salts (Ag⁺), in addition to an anti-algal treatment, then using hyperclorination as a shock, and then continuous treatment by sodium hypochlorite (NaClO). L. pneumophila serogroup 8 was found at a concentration of 5.06 Log cfu/L after the CTS filling; a shock treatment performed by H₂O₂/Ag⁺ produced a rapid increase in contamination up to 6.14 Log cfu/L. The CTS activity was stopped and two subsequent shock treatments were performed using NaClO, followed by continuous hyperclorination. These procedures showed a significant decrease (p < 0.05) in Legionella concentration (1.77 Log cfu/L). The same trend was observed for P. aeruginosa (0.55 Log cfu/100 mL) and HPC (1.95 Log cfu/mL) at 36 °C. Environmental monitoring and the adoption of maintenance procedures, including anti-scale treatment, and physical, chemical, and microbiological control, ensure the good performance of a CTS, reducing the Legionella risk for public health.
More Related Videos
14:17The Portable Chemical Sterilizer PCS, D-FENS, and D-FEND ALL: Novel Chlorine Dioxide Decontamination Technologies for the Military
Published on: June 29, 2014
12:11A Modified EPA Method 1623 that Uses Tangential Flow Hollow-fiber Ultrafiltration and Heat Dissociation Steps to Detect Waterborne Cryptosporidium and Giardia spp.
Published on: July 9, 2012
Related Concept Videos
Physical Methods for Controlling Microbial Growth: Radiation and Filtration
Cleaning, Sterilization, and Disinfection
Cleaning
The cleaning process usually involves using water with detergents or enzymatic cleaner and removing foreign material from objects and surfaces, including organic material such as body fluids or inorganic material like soil. Cleaning is performed before high-level disinfection and sterilization because foreign materials on the cover of the devices interfere with process...
Coagulation
Methods for Controlling Microbial Growth
Chemical Agents for Microbial Control
Physical Methods for Controlling Microbial Growth: Temperature