Evaluation of thermal comfort and carbon dioxide levels during ventricular-assist-device implant
Marco Lembo1, Antonio Santoro, Martina Andellini
1Direzione Tecnologie Infrastrutture e Governo dei Rischi, Funzione Risk Management e Technology Assessment, Ospedale Pediatrico Bambino Gesù - IRCCS, Roma, Italia. marco.lembo@opbg.net.
Background:
Environmental measurements were performed in an operating theatre within a pediatric cardiac department, during a surgical operation involving the use of carbon dioxide for the implantation of a ventricular system (VAD).
Objectives:
After some reports from the staff, who were complaining about low temperatures in the operating room, it was decided to check carbon dioxide levels, the conditions of thermal comfort and the presence of draughts.
Methods:
Microclimatic parameters and carbon dioxide concentration were performed with a microclimatic unit Delta OHM model HD 32.1.
Results:
The carbon dioxide concentration values measured during the operation were below the levels at which the working environment was not comfortable, as expressed by both the ASHRAE (American Society of Heating, Refrigeration and Air Conditioning Engineers) and the ACGIH (American Conference of Government Industrial Hygienists) standards. PMV (Predicted Mean Vote) and PPD (Preticted Pencentage of Dissatisfied) values obtained indicate a thermal discomfort tendency to cold perception, perceived in particular by the anesthesiologist, circulating nurse and cardiovascular perfusionist. Airflow discomforts occurred at different stages of the operation.
Conclusions:
Acting on the air conditioning system, decreasing air velocity, while guaranteeing the minimum number of air recirculation prescribed by the regulations, appears to be the best prevention measure. Changing the mode of laminar air inlet above the cot may, however, affect the "wash" effect of the operating range. Otherwise, a "protective" measure could concern staff clothes, providing them with garments with better insulation, in order to protect the neck area, which is affected by the effects of draughts.
More Related Videos
Related Concept Videos
Mechanical Ventilation II: Invasive Ventilation
Negative-Pressure Ventilators
Negative-pressure ventilators create a vacuum around the chest or body to draw air into the lungs, simulating breathing. This method does not require an...
Mechanical Ventilation III: Noninvasive Ventilation
Noninvasive Positive-Pressure Ventilation...
Mechanical Ventilation I: Indication and Settings
Assessment of Ventilation II: Respiratory Depth and Rhythm
Respiratory depth measures the volume of air inhaled or exhaled during a breath. It can vary from shallow to deep and typically remains consistent when a person is at rest or asleep. Occasionally, individuals will automatically inhale deeply, known as sighing, which inflates the lungs with more air than normal breathing.
To assess respiratory depth, observe the degree of chest excursion or movement:
Assessment of Ventilation I: Respiratory Rate
A Ventilation assessment is critical for monitoring a patient's health status. Respiration, one of the most accessible vital signs, provides insights into the function of numerous body systems and can indicate serious health issues, such as brainstem injuries from head trauma.
Critical Guidelines for Assessing Ventilation:
Assessment of Diffusion and Perfusion
The Role of Diffusion in Respiration
Diffusion is the process by which molecules move from an area of higher concentration to an area of lower concentration. In the respiratory system, this...