Related Experiment Video
Updated: Feb 11, 2026

A New Portable In Vitro Exposure Cassette for Aerosol Sampling
Published on: February 22, 2019
Sampling in schools and large institutional buildings: Implications for regulations, exposure and management of lead
Evelyne Doré1, Elise Deshommes1, Robert C Andrews2
1NSERC Industrial Chair on Drinking Water, Department of Civil, Mining and Geological Engineering, Polytechnique Montréal, Montréal, QC, Canada.
Abstract:
Legacy lead and copper components are ubiquitous in plumbing of large buildings including schools that serve children most vulnerable to lead exposure. Lead and copper samples must be collected after varying stagnation times and interpreted in reference to different thresholds. A total of 130 outlets (fountains, bathroom and kitchen taps) were sampled for dissolved and particulate lead as well as copper. Sampling was conducted at 8 schools and 3 institutional (non-residential) buildings served by municipal water of varying corrosivity, with and without corrosion control (CC), and without a lead service line. Samples included first draw following overnight stagnation (>8h), partial (30 s) and fully (5 min) flushed, and first draw after 30 min of stagnation. Total lead concentrations in first draw samples after overnight stagnation varied widely from 0.07 to 19.9 μg Pb/L (median: 1.7 μg Pb/L) for large buildings served with non-corrosive water. Higher concentrations were observed in schools with corrosive water without CC (0.9-201 μg Pb/L, median: 14.3 μg Pb/L), while levels in schools with CC ranged from 0.2 to 45.1 μg Pb/L (median: 2.1 μg Pb/L). Partial flushing (30 s) and full flushing (5 min) reduced concentrations by 88% and 92% respectively for corrosive waters without CC. Lead concentrations were <10 μg Pb/L in all samples following 5 min of flushing. However, after only 30 min of stagnation, first draw concentrations increased back to >45% than values in 1st draw samples collected after overnight stagnation. Concentrations of particulate Pb varied widely (≥0.02-846 μg Pb/L) and was found to be the cause of very high total Pb concentrations in the 2% of samples exceeding 50 μg Pb/L. Pb levels across outlets within the same building varied widely (up to 1000X) especially in corrosive water (0.85-851 μg Pb/L after 30MS) confirming the need to sample at each outlet to identify high risk taps. Based on the much higher concentrations observed in first draw samples, even after a short stagnation, the first 250mL should be discarded unless no sources of lead are present. Results question the cost-benefit of daily or weekly flushing as a remediation strategy. As such, current regulatory requirements may fail to protect children as they may not identify problematic taps and effective mitigation measures.
More Related Videos
06:52Positron Emission Tomography Using 64-Copper as a Tracer for the Study of Copper-Related Disorders
Published on: April 28, 2023
16:21Quantifying Fish Swimming Behavior in Response to Acute Exposure of Aqueous Copper Using Computer Assisted Video and Digital Image Analysis
Published on: February 26, 2016
Related Concept Videos
Epigenetic Regulation
Regulated Protein Degradation
Protein degradation plays two important roles in the cells. It helps to protect cells from misfolded or damaged proteins before they lead to a...
Movement Joints in Buildings
The simplest type of movement joints, working joints, are...
Types of Building Stone
Igneous rocks are formed from the solidification of magma or lava. An example is granite, known for its durability and resistance to weathering, making it ideal for parts of...
Covalently Linked Protein Regulators
These groups modify specific amino acids in a protein....
GTPases and their Regulation
Large G-proteins,...