Quantitative microbial risk assessment of Legionella pneumophila in a drinking water supply system in Israel
Y Sharaby1, S Rodríguez-Martínez1, M G Höfle2
1Department of Evolutionary and Environmental Biology, Faculty of Natural Sciences, University of Haifa, Haifa, Israel.
Abstract:
Legionella pneumophila cause human infections via inhalation of contaminated water aerosols, resulting in severe pneumonia. Legionella spp. prevalence was monitored in a drinking-water distribution system (DWDS) in Northern Israel. Five points (toilet faucets and showers) were sampled seasonally along a three years period. Toilet faucets and shower use, both generating aerosols, are known transmission routes for this pathogen and thus, present a potential health risk. Quantitative Microbial Risk Assessment (QMRA) was applied in order to assess the health risks posed by Legionella for these two exposure scenarios, while considering Legionella seasonality. The obtained results were compared with estimated tolerable risk levels of infection and of disease set by the USEPA and WHO. Both limits were expressed as Disability-Adjusted Life Years index (DALY) being 1 × 10-4 and 1 × 10-6, respectively. The QMRA revealed that the annual risk levels for both faucets and showers use exceeded the acceptable risk of infection with an average of 5.52 × 10-4 and 2.37 × 10-3 DALY'S per person per year, respectively. Annual risk levels were stable with no significant differences between the three years. Risk levels varied significantly between seasons by up to three orders of magnitude. Risk levels were highest during summer, autumn, and lowest during winter. The highest seasonal infection risk values were found in summer for both faucets and showers, which corresponded to 8.09 × 10-4 and 2.75 × 10-3 DALY'S per person per year, respectively. In conclusion, during summer and autumn there is a significant increase of the infection risk associated with exposure to Legionella-contaminated aerosols, in the studied water system. Public health assessment and prevention measures should focus on these seasons.
More Related Videos
09:12Applying Live Cell Imaging and Cryo-Electron Tomography to Resolve Spatiotemporal Features of the Legionella pneumophila Dot/Icm Secretion System
Published on: March 10, 2020
08:34Legionella pneumophila Outer Membrane Vesicles: Isolation and Analysis of Their Pro-inflammatory Potential on Macrophages
Published on: February 22, 2017
Related Concept Videos
Design Example: Analyzing Capacity Contours for Flood Risk Assessment
The Water Cycle
Relative Risk
Nerve Supply of the GI Tract
The enteric nervous system consists of two major plexuses: the myenteric plexus (Auerbach's plexus) and the submucosal plexus (Meissner's plexus). These plexuses are located within the layers of...
Blood Supply to the Digestive System
Blood Supply to the Digestive System: The splanchnic circulation involves three main arteries: the celiac artery (also known as the celiac trunk) and the superior and inferior mesenteric...
States of Water
Water freezes when the intermolecular forces are greater than the kinetic energy. Unlike most other substances, water is less dense in its solid state than in its liquid state. This is because each water molecule can form...