Related Experiment Video
Updated: Jan 24, 2026

Waste Water Derived Electroactive Microbial Biofilms: Growth, Maintenance, and Basic Characterization
Published on: December 29, 2013
Mitigation of microbial contamination from waste water and aerosolization by sink design
1Department of Pathology and Microbiology, University of Nebraska Medical Center, Omaha, NE, USA.
Background:
Healthcare-associated infections (HAIs) are a significant cause of increased medical costs, morbidity, mortality, and have been partly associated with sinks, their waste water outlets and associated pipework.
Aim:
To determine whether an engineered sink could limit microbial aerosol contaminants in the air and sink basin.
Methods:
Multiple comparisons were undertaken between an experimental sink, designed to limit aerosolization and p-trap contamination to a control hospital sink, both connected to a common drain system. The experimental sink was equipped with ultraviolet light (UV), an aerosol containment hood, ozonated water generator and a flush system to limit bacterial growth/aerosolization and limit microbial growth in the p-trap. Nutrient material was added daily to simulate typical material discarded into a hospital sink. Surface collection swabs, settle plates and p-trap contamination levels were assessed for bacteria and fungi.
Findings:
The experimental sink had significantly decreased levels of bacterial and fungal p-trap contamination (99.9% for Tryptic Soy (TSA) and Sabouraud agar (SAB) plates) relative to the initial levels. Aerosol-induced contaminant from the p-traps was significantly lower for the experimental vs the control sink for TSA (76%) and SAB (86%) agar settle plates.
Conclusions:
Limiting microbial contamination is critical for the control of nosocomial infections of in-room sinks, which provide a major source of contamination. Our experimental sink studies document that regular ozonated water rinsing of the sink surface, decontamination of p-trap water, and UV decontamination of surfaces limits microbial aerosolization and surface contamination, with potential to decrease patient exposure and reduce hospital acquired infections.
Related Concept Videos
Design Example: Designing Water Slide
Bernoulli's principle determines the water's velocity along the slide....
Contaminants and Errors
Another key consideration is determining the appropriate number of samples required to...
Group Design
States of Water
Water freezes when the intermolecular forces are greater than the kinetic energy. Unlike most other substances, water is less dense in its solid state than in its liquid state. This is because each water molecule can form...
Factorial Design
Microbial Morphologies