Case study of sulfide generation and emission in sanitary sewer with drop structures and pump station
Zhi Yang1, David Z Zhu1, Tong Yu1
1Department of Civil and Environmental Engineering, University of Alberta, Edmonton, AB, T6G 2W2, Canada
Abstract:
Field work was carried out to identify sewer odor hotspots and corresponding causes in a sanitary sewer trunk with drop structures and pump station in Steinhauer area, Edmonton, Canada. Relatively high concentrations of H2S were detected at the beginning and the end of the trunk with odor complaints. At the beginning of the trunk, sulfide emission was mainly caused by the increased stripping effect of the drop structures. The pump operation at the end of the trunk causes the long retention time of the sewage and the subsequent sulfide generation. The sulfide generation was modeled and calibrated using field measurements. The model was applied to assess mitigation strategies, and optimized pump operation was found to be able to reduce sulfide generation in the study trunk sewer.
Related Concept Videos
Structure and Nomenclature of Thiols and Sulfides
Preparation and Reactions of Sulfides
Emission Spectra
Ionic Crystal Structures
Most monatomic ions behave as charged spheres, and their attraction for ions of opposite charge is the same in every direction. Consequently, stable structures for ionic compounds result (1) when ions of one charge are surrounded by as many ions as possible of the opposite...
Imaging Studies II: Positron Emission Tomography and Scintigraphy
Fundamental Principles of PET
ATP Driven Pumps III: V-type Pumps
The peripheral or cytosolic V1 domain with eight subunits is involved in ATP hydrolysis. The integral or transmembrane V0 domain containing at least five subunits...