Related Experiment Video
Updated: Jan 22, 2026

Using Insect Electroantennogram Sensors on Autonomous Robots for Olfactory Searches
Published on: August 4, 2014
Self-Calibration of Nonlinear Signal Model for Angular Position Sensors by Model-Based Automatic Search Algorithm
Zhenyi Gao1, Bin Zhou2, Bo Hou3
1Engineering Research Center for Navigation Technology, Department of Precision Instrument, Tsinghua University, Beijing 100084, China. gaozy17@mails.tsinghua.edu.cn.
Abstract:
This study proposes a novel model-based automatic search algorithm to realize the self-calibration of nonlinear signal model for angular position sensors. In some high-precision angular position sensors, nonlinearity of the signal model is the main source of errors and cannot be handled effectively. By constructing a signal flow network framework and by embedding a modeling search network, the parameters of the nonlinear signal model can be searched, and the calibration signal can be obtained. The convergence of the network search process was analyzed. The relationship between the optimization threshold and the convergence accuracy was also studied in simulations. Compared with the maximum angular error reduction to 47.42% after the calibration with simplified model that ignores signal nonlinearities, the proposed scheme was able to reduce this error to 0.0025% in simulations. By implementing the technique in a capacitive angular position sensor, the experimental results showed that the maximum angular error was reduced to 1.63% compared to a reduction of 86.02% achieved with the simplified model calibration. The effects of the search network order and layer number on the calibration accuracy were also analyzed, and the optimal parameters under experimental conditions were obtained. Correspondingly, the proposed scheme is able to handle calibration of nonlinear signal model and further improve sensor accuracy.
Related Concept Videos
Mechanistic Models: Compartment Models in Algorithms for Numerical Problem Solving
In individual population analyses, different algorithms are employed, such as Cauchy's method, which uses a...
Small-signal Diode Model
Drug Distribution as One-Compartment Model and Elimination by Nonlinear Pharmacokinetics: Overview
For instance, consider the metabolism of sodium salicylate. This compound is metabolized into two distinct substances: a glucuronide and a glycine conjugate. The rate of conjugation depends...
Parameters Affecting Nonlinear Elimination: Zero-Order Input, First-Order Absorption and Two-Compartment Model
When a drug is administered through a constant intravenous infusion and eliminated via nonlinear pharmacokinetics, it follows zero-order input. For example, oral drugs undergo first-order absorption upon administration and are eliminated through nonlinear pharmacokinetics.
In the case of subcutaneously administered drugs,...
Nonlinear Pharmacokinetics: Causes of Nonlinearity
Nonlinear drug absorption can occur when the process is rate-limited by solubility, carrier-mediated transport systems, or saturation of the presystemic gut wall or hepatic metabolism. For instance, high doses of riboflavin...
Automatic Processing and Automatic Social Behavior