Related Experiment Video
Updated: Dec 25, 2025

A Novel Technique for Raman Analysis of Highly Radioactive Samples Using Any Standard Micro-Raman Spectrometer
Published on: April 12, 2017
Multigas Analysis by Cavity-Enhanced Raman Spectroscopy for Power Transformer Diagnosis
Pinyi Wang1, Weigen Chen1, Jianxin Wang1
1State Key Laboratory of Power Transmission Equipment & System Security and New Technology, Chongqing University, No. 174, Shazheng Street, Chongqing, 400044, China.
Abstract:
We demonstrate the utility of cavity-enhanced Raman spectroscopy (CERS) as a unique multigas analysis tool for power transformer diagnosis. For this purpose, improvements have been added to our recently introduced CERS apparatus. Based on optical feedback frequency-locking, laser radiation is coupled into a high-finesse optical cavity, thus resulting in huge intracavity laser power. With 20 s exposure time, ppm-level gas sensing at 1 bar total pressure is achieved, including carbon dioxide (CO2), carbon monoxide (CO), hydrogen (H2), methane (CH4), ethane (C2H6), ethylene (C2H4), acetylene (C2H2), nitrogen (N2), and oxygen (O2). By using the internal standard gas (sulfur hexafluoride, SF6), the quantification of multigas with high accuracy is also realized, which is confirmed by the measurement of calibration gases. For fault diagnosis, transformer oil is sampled from a 110 kV power transformer in service. Dissolved gases are extracted and analyzed by the CERS apparatus. Then the transformer is diagnosed according to the measurement results. CERS has the ability to analyze multigas with high selectivity, sensitivity, and accuracy, it has great potential in gas sensing fields.
Related Concept Videos
Raman Spectroscopy Instrumentation: Overview
The monochromatic laser source, typically using visible or near-infrared radiation, generates a highly focused beam of light. This light interacts with the molecules of the sample, scattering some of the light. Liquid and gaseous samples are usually tested in ordinary glass capillaries, while solids can be analyzed as powders packed in capillaries or as potassium...
Raman Spectroscopy: Overview
However, a small fraction of the scattered light exhibits a frequency shift due to the exchange of energy between the incident photons and...
Instrument Transformers
Energy Losses in Transformers
There are four main reasons for energy losses in transformers.
The first cause can be the high resistance of the...
Equivalent Circuits for Practical Transformers
In a practical transformer, each winding exhibits resistance and leakage reactance. The...
Three-Winding Transformers
In the per-unit equivalent circuit of a grounded Y-Y three-phase...