Effect of shield placement for transient voltage mitigation due to switching surges in a 33/11 kV transformer
Avinash Srikanta Murthy1, Norhafiz Azis1,2, Jasronita Jasni1
1Advanced Lightning, Power and Energy Research Centre (ALPER), Department of Electrical and Electronic Engineering, Faculty of Engineering, Universiti Putra Malaysia, Serdang, Selangor, Malaysia.
Abstract:
This study presents an investigation on the effect of shield placement for mitigation of transient voltage in a 33/11 kV, 30 MVA transformer due to Standard Switching Impulse (SSI) and Oscillating Switching Impulse (OSI) surges. Generally, the winding and insulation in transformers could experience severe voltage stress due to the external impulses i.e. switching events. Hence, it is important to examine the voltage stress and identify the mitigation action i.e. shield placements in order to reduce the adverse effect to the transformer windings. First, the resistances, inductances, and capacitances (RLC) were calculated for disc type transformer in order to develop the winding RLC equivalent circuit. The SSI and OSI transient voltage waveforms were applied to the High Voltage (HV) winding whereby the transient voltages were simulated for each disc. The resulting voltage stresses were mitigated through different configurations of electrostatic shield placements. The resonant oscillations generated due to switching surges were analysed through initial voltage distribution. The analyses on the transient voltages of the transformer winding and standard error of the slope (SEb) reveal that the location of shield placement has a significant effect on the resonant switching voltages. The increment of the shield number in the windings does not guarantee optimize mitigation of the resonant switching transient voltages. It is found that the voltage stress along the windings is linear once a floating shield is placed between the HV and Low Voltage (LV) windings of the disc-type transformer under the SSI and OSI waveforms. These findings could assist the manufacturers with appropriate technical basis for mitigation of the transformer winding against the external transient switching overvoltage surges.
Related Concept Videos
Power System Three-Phase Short Circuits
Insulation Coordination
Three-Phase Short Circuit—Unloaded Synchronous Machine
This behavior occurs due to the magnetic flux produced by the short-circuit armature currents. Initially, these currents follow high-reluctance paths but eventually shift to...
Bus Impedance Matrix
In the first circuit, all machine voltage sources are short-circuited, leaving only the prefault voltage source at the fault location. The positive-sequence bus impedance matrix can be determined by solving the nodal equations,...
Reducing Line Loss
With a step-up transformer at the source, the voltage is increased, thereby reducing the current in the transmission lines since power loss in...
Differential Relays