CFD investigation on gas-solid two-phase flow of dust removal characteristics for cartridge filter: a case study
Danhong Gao1,2, Gang Zhou3,4,5, Rulin Liu1,2
1College of Safety and Environmental Engineering, Shandong University of Science and Technology, Qingdao, 266590, People's Republic of China.
Abstract:
The filter cartridge dust collector has been widely used in industry, but the influence of its internal structure on its operation effects is rarely studied. FLUENT software was used to simulate the influence of different air volume and permeability values on the gas-solid two-phase flow of dust removal characteristics for a filter cartridge. The results show that when the air volume of the fan was greater than 1600 m3/h, the increase in the dust reduction rate was not obvious, and the high-velocity airflow filled the entire dust removal chamber, which was conducive to the filter using the largest effective filtration area to remove dust; the optimal air volume was 1600 m3/h. Furthermore, the dust removal effect gradually became worse when the porosity was higher than 0.65, but the fluidity of the internal air was poor when it was lower than 0.65. The optimum porosity was 0.65. A simulated validation analysis was conducted using the above optimal parameters. As the proportion of particles below 2 μm increased, the dust removal effect worsened.
More Related Videos
10:36Author Spotlight: Optimization of Airflow Velocities in Battery Cooling Systems for Enhanced Thermal Performance and Reduced Energy Consumption
Published on: November 3, 2023
07:10Production of Membrane-Filtered Phase-Shift Decafluorobutane Nanodroplets from Preformed Microbubbles
Published on: March 23, 2021
Related Concept Videos
Filtration
Gas Chromatography: Types of Detectors-II
Gas Chromatography: Types of Detectors-I
TCD is the earliest and most widely used detector that operates by measuring the changes in the thermal conductivity of the carrier gas. When a sample compound enters the detector,...
Gas Chromatography: Types of Columns and Stationary Phases
For an analyte to remain on the column for a sufficient amount of time, it must exhibit some level of compatibility (or...
Supercritical Fluid Chromatography
SFC utilizes a supercritical fluid mobile phase,...