Design and Construction of a Biosafety Level 3 Autopsy Laboratory

Kurt B Nolte1, Timothy B Muller2, Adam M Denmark3

  • 1From the Office of the Medical Investigator and Departments of Pathology and Radiology (Nolte [https://orcid.org/0000-0003-0257-6284]), University of New Mexico Health Science Center, Albuquerque.

Abstract

Insights

Autopsy workers face high infection risks. Designing autopsy laboratories at biosafety level 3 is crucial for worker safety and public health, especially with emerging infectious diseases.

Area of Science:

  • Public Health
  • Infectious Diseases
  • Pathology

Background:

  • Autopsy pathologists play a vital role in public health surveillance, identifying causes of death and understanding novel infections.
  • Autopsy procedures present significant biosafety risks, with autopsy workers experiencing the highest rates of laboratory-acquired infections.
  • Exposure to blood-borne pathogens (e.g., HIV, Hepatitis C) and airborne agents (e.g., Mycobacterium tuberculosis) is a constant hazard.

Purpose of the Study:

  • To design and construct an autopsy laboratory that ensures an appropriate level of biosafety for personnel.
  • To mitigate the risks associated with handling infectious agents during post-mortem examinations.

Main Methods:

  • A biosafety risk assessment was conducted for autopsy workers, following established guidelines from the US Centers for Disease Control and Prevention and National Institutes of Health.
  • The findings from the risk assessment informed the design and construction of the autopsy laboratory.

Main Results:

  • Hazardous autopsy procedures, including dissection and aerosol-generating activities, increase exposure risks.
  • The study indicates that human autopsies should be conducted at Biosafety Level 3 (BSL-3) due to potential exposure to blood-borne and airborne pathogens.
  • A large, fully BSL-3 medical examiner autopsy laboratory was designed using a concentric ring containment strategy with controlled access zones.

Conclusions:

  • Human autopsies should be performed at Biosafety Level 3 to protect workers from infectious agents.
  • New autopsy laboratories should be uniformly designed to operate at BSL-3, incorporating scalable principles for various settings.
  • Implementing BSL-3 standards in autopsy laboratory design is essential for safeguarding public health and laboratory personnel.