Legionnaires' disease associated with a hospital water system. A five-year progress report on continuous
C M Helms1, R M Massanari, R P Wenzel
1Department of Internal Medicine, University of Iowa College of Medicine, Iowa City.
Abstract:
In 1981, sixteen cases of nosocomial legionellosis occurred among 456 patients admitted to a new hematology-oncology unit (35 per 1000 admissions). Monoclonal antibody typing and restriction endonuclease plasmid analysis identified a unique strain (09,04) of Legionella pneumophila serogroup 1 isolated from both patients and water outlets. Continuous hyperchlorination of the hot and cold water began in January 1982, and chlorine levels of 3 to 5 mg/L have been maintained most recently. Water samples have been consistently negative for Legionella for more than five years. Four sporadic cases of nosocomial legionellosis have occurred in the hematology-oncology unit during the same period (one per 1000 admissions) associated with a different strain of L pneumophila serogroup 1 (09,00). The environmental reservoir(s) of L pneumophila serogroup 1 in these cases has not been identified. Levels of trihalomethanes (potential carcinogens) were high (greater than 100 micrograms/L) when chlorine levels of hot water exceeded 4 mg/L. Some corrosion damage to the water distribution system has occurred: the average number of leaks per month increased steadily from zero in 1982 to 5.2 in 1986. The chlorinator installation costs were +75,800, and annual operation expenses were +12,500. Continuous hyperchlorination is a promising but still experimental technique for control of nosocomial legionellosis. In our experience, epidemic disease has been controlled, but sporadic cases have continued to occur.
Insights
Continuous hyperchlorination controlled epidemic nosocomial legionellosis in a hematology-oncology unit. However, sporadic cases of Legionella pneumophila serogroup 1 infection persisted, with unidentified environmental reservoirs.
Area of Science:
- Infectious Diseases
- Environmental Health
- Hospital Epidemiology
Background:
- Nosocomial legionellosis outbreaks pose significant risks in healthcare settings, particularly in immunocompromised patient populations.
- Legionella pneumophila serogroup 1 was identified as the causative agent in an initial outbreak within a new hematology-oncology unit.
- The water distribution system was implicated as the environmental reservoir for the initial outbreak.
Purpose of the Study:
- To evaluate the efficacy of continuous hyperchlorination in controlling nosocomial legionellosis outbreaks.
- To assess the long-term impact of hyperchlorination on Legionella contamination in hospital water systems.
- To investigate the occurrence of sporadic legionellosis cases following the implementation of hyperchlorination.
Main Methods:
- Monoclonal antibody typing and restriction endonuclease plasmid analysis were used for strain identification.
- Continuous hyperchlorination of hot and cold water systems was implemented at 3-5 mg/L chlorine levels.
- Water samples were monitored for Legionella presence, and patient cases were tracked over time.
Main Results:
- Continuous hyperchlorination successfully eliminated the epidemic strain (09,04) of Legionella pneumophila serogroup 1 from the water system for over five years.
- Four sporadic cases of nosocomial legionellosis, linked to a different strain (09,00), occurred post-hyperchlorination, with unidentified environmental sources.
- Elevated trihalomethane levels (potential carcinogens) were observed at chlorine concentrations above 4 mg/L, and system corrosion increased.
Conclusions:
- Continuous hyperchlorination effectively controlled epidemic nosocomial legionellosis but did not eliminate sporadic cases.
- The environmental reservoir for sporadic Legionella pneumophila serogroup 1 infections remains unidentified, necessitating further investigation.
- While promising, continuous hyperchlorination is an experimental control technique with potential side effects like increased trihalomethanes and system corrosion.