Related Experiment Video
Updated: Nov 7, 2025

In Situ Visualization of the Phase Behavior of Oil Samples Under Refinery Process Conditions
Published on: February 21, 2017
Aging Characteristics of Transformer Oil-Impregnated Insulation Paper Based on Trap Parameters
Yanhui Wei1, Wang Han1, Guochang Li1
1Institute of Advanced Electrical Materials, Qingdao University of Science and Technology, Qingdao 266042, China.
Abstract:
Oil-impregnated insulation paper is an important part of transformers; its performance seriously affects the life of power equipment. It is of significance to study the aging characteristics and mechanism of oil-impregnated insulation paper under thermal stress for transformer status detection and evaluation. In the work, the accelerated thermal aging was carried out at 120 °C, and DP1490, DP787, and DP311 samples were selected to represent the new, mid-aging, and late-aging status of the transformer, respectively. The space charge distribution within the specimens was measured by the pulsed electro-acoustic (PEA) method and the trap parameters were extracted based on the measurement curves. Further, the aging mechanism was studied by molecular simulation technology. A typical molecular chain defect model was constructed to study the motion of cellulose molecules under thermal stress. The experimental results show that the corresponding trap energy levels are 0.54 eV, 0.73 eV, and 0.92 eV for the new specimen, the mid-aging specimen, and the late aging specimen, respectively. The simulation results show that the trapped energy at the beginning of aging is mainly determined by the loss of H atoms. The changes in trap energy in the middle stage of aging are mainly caused by the absence of some C atoms, and the trap energy level at the end of aging is mainly caused by the breakage of chemical bonds. This study is of great significance to reveal the aging mechanism of oil-impregnated insulation paper and the modification of insulation paper.
Related Concept Videos
Transformers in Distribution System
Distribution substation transformers come in various ratings and typically use mineral oil for insulation and cooling. To prevent moisture and air from entering the oil, some transformers use an inert gas like nitrogen to fill the...
Insulation Coordination
Energy Losses in Transformers
There are four main reasons for energy losses in transformers.
The first cause can be the high resistance of the...
Equivalent Circuits for Practical Transformers
In a practical transformer, each winding exhibits resistance and leakage reactance. The...
Three-Winding Transformers
In the per-unit equivalent circuit of a grounded Y-Y three-phase...
Instrument Transformers