Related Experiment Video
Updated: Nov 6, 2025

Interactive and Visualized Online Experimentation System for Engineering Education and Research
Published on: November 24, 2021
Heat recovery steam generator (HRSG) three-element drum level control utilizing Fractional order PID and fuzzy
Mostafa A Elhosseini1, Ahmed Shams El-Din2, Hesham Arafat Ali3
1Taibah University, College of computer science and Engineering in Yanbu, Madinah, Saudi Arabia; Mansoura University, Computers Engineering and control systems Dept., Faculty of Engineering, Egypt.
Abstract:
Shrink and swell is a phenomenon that causes transient variability in water level once boiler load variation occurs. The leading cause of the swell effect is the steam demand changes and the actual arrangement of steam generating tubes in the boiler. Steam bubbles beneath HRSG drum water make the level control very difficult, particularly with significant disturbances in the input heat to HRSG. Plant shutdown may occur in some situations, and combined cycle plant efficiency is diminished. The recently applied control methods in industry are single-element and three-element control with PID controllers, but these methods are not well suited for substantial load changes. The main aim of this paper is to investigate the shrink and swell phenomenon inside HRSG power plants. In addition to the existing PID loops, two different standalone controllers, namely, the FOPID controller and fuzzy controller, are implemented with the HRSG model. Besides, Artificial Bee Colony (ABC) algorithm is used to tune FOPID efficiently. Based on overshoot, rise time, ISE, IAE, ITAE as performance measures, the comparison has been held between the three controllers. Simulations show that how the ABC optimization algorithm is efficient with PID, FOPID. It turns out that the proposed method is capable of improving system responses compared to the conventional optimal controller.
Related Concept Videos
PID Controller
Time and frequency -Domain Interpretation of PI Control
Acting as a low-pass filter, the PI controller slows the system's response and extends settling times. This requires...
PD Controller: Design
Designing a continuous-data controller requires selecting and linking components like adders and integrators, which are fundamental in Proportional,...
PI Controller: Design
Time-Domain Interpretation of PD Control
Consider the example of control of motor torque. Initially, a positive...
Frequency-Domain Interpretation of PD Control
The proportional control gain, combined with the...