Quasirandom Graphs and the Pantograph Equation

The American Mathematical Monthly : the Official Journal of the Mathematical Association of America
|August 30, 2021
PubMed

Related Concept Videos

Vector Algebra: Graphical Method01:10

Vector Algebra: Graphical Method

Vectors can be multiplied by scalars, added to other vectors, or subtracted from other vectors. The vector sum of two (or more) vectors is called the resultant vector or, for short, the resultant.
We use the laws of geometry to construct resultant vectors, followed by trigonometry to find vector magnitudes and directions. For a geometric construction of the sum of two vectors in a plane, we follow the parallelogram rule. Suppose two vectors are at arbitrary positions. Translate either one of...
15.5K
Sequence Networks of Rotating Machines01:24

Sequence Networks of Rotating Machines

A Y-connected synchronous generator, grounded through a neutral impedance, is designed to produce balanced internal phase voltages with only positive-sequence components. The generator's sequence networks include a source voltage that is exclusively in the positive-sequence network. The sequence components of line-to-ground voltages at the generator terminals illustrate this configuration.
Zero-sequence current induces a voltage drop across the generator's neutral impedance and other...
180
Routh-Hurwitz Criterion II01:19

Routh-Hurwitz Criterion II

In the application of the Routh-Hurwitz criterion, two specific scenarios can arise that complicate stability analysis.
The first scenario occurs when a singular zero appears in the first column of the Routh table. This situation creates a division by zero issues. To resolve this, a small positive or negative number, denoted as epsilon (∈), is substituted for the zero. The stability analysis proceeds by assuming a sign for ∈. If ∈ is positive, any sign change in the first...
508
The Power Flow Problem and Solution01:26

The Power Flow Problem and Solution

Power flow problem analysis is fundamental for determining real and reactive power flows in network components, such as transmission lines, transformers, and loads. The power system's single-line diagram provides data on the bus, transmission line, and transformer. Each bus k in the system is characterized by four key variables: voltage magnitude Vk​, phase angle δk​, real power Pk​, and reactive power Qk​. Two of these four variables are inputs, while the...
399
Parallel-axis Theorem01:06

Parallel-axis Theorem

The parallel-axis theorem provides a convenient and quick method of finding the moment of inertia of an object about an axis parallel to the axis passing through its center of mass. Consider a thin rod as an example. There is a striking similarity between the process of finding the moment of inertia of a thin rod about an axis through its middle, where the center of mass lies, and about an axis through its end using the conventional method. In the conventional method, the concept of linear mass...
7.3K
Routh-Hurwitz Criterion I01:15

Routh-Hurwitz Criterion I

Consider an electrical power grid, where stability is essential to prevent blackouts. The Routh-Hurwitz criterion is a valuable tool for assessing system stability under varying load conditions or faults. By analyzing the closed-loop transfer function, the Routh-Hurwitz criterion helps determine whether the system remains stable.
To apply the Routh-Hurwitz criterion, a Routh table is constructed. The table's rows are labeled with powers of the complex frequency variable s, starting from the...
368