Pontiac fever outbreak associated with a cooling tower.
American Journal of Public Health
|May 1, 1987
Summary
An investigation into a Pontiac fever outbreak in a New York City office building revealed airborne spread of Legionella pneumophila from a cooling tower, causing widespread illness.
Area of Science:
- Environmental microbiology
- Public health
- Infectious disease epidemiology
Background:
- Pontiac fever is a mild, flu-like illness caused by Legionella bacteria.
- Outbreaks are often linked to contaminated water systems, particularly cooling towers.
- Identifying the source and transmission route is crucial for preventing further spread.
Purpose of the Study:
- To investigate the cause and transmission of a Pontiac fever outbreak in a Manhattan office building.
- To identify the specific pathogen and its environmental source.
- To assess the effectiveness of control measures.
Main Methods:
- Epidemiological investigation including case finding and symptom analysis.
- Environmental sampling of the building's cooling tower and air intake system.
- Microbiological analysis of water and air samples for Legionella pneumophila.
- Serological testing and monoclonal antibody typing of bacterial isolates.
Main Results:
- A high attack rate (78%) of Pontiac fever was observed among building occupants.
- Legionella pneumophila serogroup 1 was identified in high concentrations in the dedicated cooling tower.
- Airborne transmission was confirmed via settle plates in the air intake and affected office.
- The organism was difficult to eradicate from the cooling tower.
Conclusions:
- The office building's cooling tower was the source of the Pontiac fever outbreak.
- Airborne dissemination from the cooling tower led to widespread infection.
- Effective disinfection and maintenance are critical for preventing Legionella outbreaks in building water systems.