Pontiac fever outbreak associated with a cooling tower

Insights

An investigation into a Pontiac fever outbreak in a New York City office building revealed airborne spread of Legionella pneumophila from a cooling tower, causing widespread illness.

Area of Science:

  • Environmental microbiology
  • Public health
  • Infectious disease epidemiology

Background:

  • Pontiac fever is a mild, flu-like illness caused by Legionella bacteria.
  • Outbreaks are often linked to contaminated water systems, particularly cooling towers.
  • Identifying the source and transmission route is crucial for preventing further spread.

Purpose of the Study:

  • To investigate the cause and transmission of a Pontiac fever outbreak in a Manhattan office building.
  • To identify the specific pathogen and its environmental source.
  • To assess the effectiveness of control measures.

Main Methods:

  • Epidemiological investigation including case finding and symptom analysis.
  • Environmental sampling of the building's cooling tower and air intake system.
  • Microbiological analysis of water and air samples for Legionella pneumophila.
  • Serological testing and monoclonal antibody typing of bacterial isolates.

Main Results:

  • A high attack rate (78%) of Pontiac fever was observed among building occupants.
  • Legionella pneumophila serogroup 1 was identified in high concentrations in the dedicated cooling tower.
  • Airborne transmission was confirmed via settle plates in the air intake and affected office.
  • The organism was difficult to eradicate from the cooling tower.

Conclusions:

  • The office building's cooling tower was the source of the Pontiac fever outbreak.
  • Airborne dissemination from the cooling tower led to widespread infection.
  • Effective disinfection and maintenance are critical for preventing Legionella outbreaks in building water systems.