A Power-Line Communication System Governed by Loop Resonance for Photovoltaic Plant Monitoring

José Ignacio Morales-Aragones1, Matthew St Michael Williams2, Halleluyah Kupolati3

  • 1Departamento de Física, Universidad de Valladolid, 42004 Soria, Spain.

Related Concept Videos

Line Protection with Impedance Relays01:27

Line Protection with Impedance Relays

Coordinating time-delay overcurrent relays in complex radial systems and directional overcurrent relays in multi-source transmission loops can be challenging. Impedance relays address these issues by responding to the voltage-to-current ratio, specifically measuring the apparent impedance of a line. These relays become more sensitive during faults as current increases and voltage decreases, thereby reducing the apparent impedance.
Under normal conditions, low load currents keep the measured...
121
Power Factor Correction01:20

Power Factor Correction

The power transmission to a factory involves the transfer of apparent power, a combination of active and reactive power. The power factor measures how effectively electrical power is converted into useful work output. The ratio of the real power (KW) that does the work to the apparent power (KVA) supplied to the circuit.
240
Power System Distribution01:25

Power System Distribution

Power system distribution involves delivering electrical energy from power plants to consumers through a network of transmission and distribution systems. The process begins at power plants, where energy from coal, gas, nuclear, water, and wind is converted into electrical energy. These plants use three-phase generators, typically rated between 50 to 1300 MVA, with terminal voltages ranging from a few kV to 20 kV, depending on the size and age of the units.
The transmission system is designed...
297
Parallel Resonance01:23

Parallel Resonance

The parallel RLC circuit is an arrangement where the resistor (R), inductor (L), and capacitor (C) are all connected to the same nodes and, as a result, share the same voltage across them. The parallel RLC circuit is analyzed in terms of admittance (Y), which reflects the ease with which current can flow. The admittance is given by:
251
Power System Three-Phase Short Circuits01:21

Power System Three-Phase Short Circuits

Determining the subtransient fault current in a power system involves representing transformers by their leakage reactances, transmission lines by their equivalent series reactances, and synchronous machines as constant voltage sources behind their subtransient reactances. In this analysis, certain elements are excluded, such as winding resistances, series resistances, shunt admittances, delta-Y phase shifts, armature resistance, saturation, saliency, non-rotating impedance loads, and small...
135
Maximum Power Flow and Line Loadability01:23

Maximum Power Flow and Line Loadability

The maximum power flow for lossy transmission lines is derived using ABCD parameters in phasor form. These parameters create a matrix relationship between the sending-end and receiving-end voltages and currents, allowing the determination of the receiving-end current. This relationship facilitates calculating the complex power delivered to the receiving end, from which real and reactive power components are derived.
158