Acoustic Noise-Based Detection of Ferroresonance Events in Isolated Neutral Power Systems with Inductive Voltage
Raquel Martinez1, Alberto Arroyo1, Alberto Pigazo2
1Departamento de Ingeniería Eléctrica y Energética, Universidad de Cantabria, Av. Los Castros s/n, 39005 Santander, Spain.
Abstract:
Power-quality events and operation transients in power systems (PS) with isolated neutral can saturate inductive voltage transformers (IVT), which, when interacting with the overhead and underground cable capacitances, can cause ferroresonance events in the local PS. This abnormal operating mode can partially or totally damage the transformers and switchgears within the affected PS. Distribution system operators (DSO) can minimize these effects by detecting ferroresonance events accurately and fast enough and changing the mode of operation accordingly. Direct detection methods, i.e., based on voltage measurements, are reliable, but the massive deployment of this solution is relatively expensive; i.e., power quality analyzers cost thousands of USD. Alternatively, indirect detection methods are also available, e.g., IVT vibration measurements with accelerometers costing hundreds of USD, but their reliability depends on the installation method used. This manuscript proposes using the acoustic noise caused by magnetostriction forces within the IVT core during ferroresonance events to detect their occurrence. Compared to other indirect methods, electret condenser microphones with preamplifying stage cost less than USD 10 and are less sensitive to the installation procedure. The proposed method is validated experimentally, and its performance compared to IVT vibration measurements one by using the same detection methodology.
More Related Videos
06:45Design and Application of a Fault Detection Method Based on Adaptive Filters and Rotational Speed Estimation for an Electro-Hydrostatic Actuator
Published on: October 28, 2022
11:18A Guide to Concentration Alternating Frequency Response Analysis of Fuel Cells
Published on: December 11, 2019
Related Concept Videos
Power System Three-Phase Short Circuits
Instrument Transformers
Line Protection with Impedance Relays
Under normal conditions, low load currents keep the measured...
Energy Losses in Transformers
There are four main reasons for energy losses in transformers.
The first cause can be the high resistance of the...
Reclosers and Fuses
A comprehensive protection scheme for radial distribution...
Three-Phase Short Circuit—Unloaded Synchronous Machine
This behavior occurs due to the magnetic flux produced by the short-circuit armature currents. Initially, these currents follow high-reluctance paths but eventually shift to...