Related Experiment Video
Updated: May 28, 2026

Development of a Rabbit Chronic-Like Rotator Cuff Injury Model for Study of Fibrosis and Muscular Fatty Degeneration
Published on: March 31, 2023
Development and clinical validation of deep learning for auto-diagnosis of supraspinatus tears
Deming Guo1,2, Xiaoning Liu1, Dawei Wang3
1Orthopaedic Medical Center, The Second Hospital of Jilin University, Changchun, 130041, People's Republic of China.
Background:
Accurately diagnosing supraspinatus tears based on magnetic resonance imaging (MRI) is challenging and time-combusting due to the experience level variability of the musculoskeletal radiologists and orthopedic surgeons. We developed a deep learning-based model for automatically diagnosing supraspinatus tears (STs) using shoulder MRI and validated its feasibility in clinical practice.
Materials And Methods:
A total of 701 shoulder MRI data (2804 images) were retrospectively collected for model training and internal test. An additional 69 shoulder MRIs (276 images) were collected from patients who underwent shoulder arthroplasty and constituted the surgery test set for clinical validation. Two advanced convolutional neural networks (CNN) based on Xception were trained and optimized to detect STs. The diagnostic performance of the CNN was evaluated according to its sensitivity, specificity, precision, accuracy, and F1 score. Subgroup analyses were performed to verify its robustness, and we also compared the CNN's performance with that of 4 radiologists and 4 orthopedic surgeons on the surgery and internal test sets.
Results:
Optimal diagnostic performance was achieved on the 2D model, from which F1-scores of 0.824 and 0.75, and areas under the ROC curves of 0.921 (95% confidence interval, 0.841-1.000) and 0.882 (0.817-0.947) were observed on the surgery and internal test sets. For the subgroup analysis, the 2D CNN model demonstrated a sensitivity of 0.33-1.000 and 0.625-1.000 for different degrees of tears on the surgery and internal test sets, and there was no significant performance difference between 1.5 and 3.0 T data. Compared with eight clinicians, the 2D CNN model exhibited better diagnostic performance than the junior clinicians and was equivalent to senior clinicians.
Conclusions:
The proposed 2D CNN model realized the adequate and efficient automatic diagnoses of STs, which achieved a comparable performance of junior musculoskeletal radiologists and orthopedic surgeons. It might be conducive to assisting poor-experienced radiologists, especially in community scenarios lacking consulting experts.
Related Concept Videos
Knee Joint
A total of seven ligaments support the knee joint. The patellar ligament, which is also attached to the quadriceps femoris group...
Degenerative Disc Disease I: Introduction
Degenerative Disc Disease ll: Pathophysiology