Diagnosis Method of Decay-like Composite Insulators in a High-Humidity Environment Based on Characteristic
Yuming Zhang1, Sizu Hou2, Jianghai Geng1
1Hebei Key Laboratory of Power Transmission Equipment Security Defense, North China Electric Power University, Baoding 071003, China.
Abstract:
At present, the temperature rise in insulators is observed using infrared thermometry as a common method of diagnosing decay-like insulators. However, the original characteristic data obtained by infrared thermometry cannot effectively distinguish some of the decay-like insulators from those with ageing sheaths. Therefore, it is imperative to find a new diagnostic characteristic quantity. Based on statistical data, this article first explains that existing diagnostic methods have limited diagnostic effectiveness and a high false detection rate for insulators in a slightly heated state. A full-scale temperature rise test is carried out on a batch of composite insulators returned from the field under high-humidity conditions. Two different defective insulators with similar temperature rise profiles are identified, and an electro-thermal coupling simulation model is developed based on the dielectric characteristic parameters of the above insulators for both core rod defects and sheath ageing. A new infrared diagnostic feature, the temperature rise gradient coefficient, is then obtained to identify the source of abnormal heat in insulators using statistical analysis of an infrared image gallery of abnormally hot composite insulators obtained from field inspections and laboratory tests.