Related Experiment Video
Updated: Jul 16, 2025

Cutting Procedures, Tensile Testing, and Ageing of Flexible Unidirectional Composite Laminates
Published on: April 27, 2019
Study on Deterioration Characteristics of a Composite Crossarm Mandrel in a 10 kV Distribution Network Based on
Long Ma1,2, Xiaotao Fu1, Lincong Chen1
1Key Laboratory of Physical and Chemical Analysis for Electric Power of Hainan Province, Hairui Road No. 23, Haikou 570100, China.
Abstract:
This paper presents a study that conducted 5000 h of multi-factor aging tests on 10 kV composite crossarms, considering the natural environment in coastal areas and actual power line operations. Various aging conditions, such as voltage, rain, temperature, humidity, salt fog, ultraviolet light, and mechanical stress, were applied during the tests. The research initially analyzed the influence of multi-factor aging on the bending and tensile properties of the full-size composite crossarm. Subsequently, a detailed investigation was carried out to assess the impact of aging on the mechanical properties, electrical insulation properties, and microscopic characteristics of the composite crossarm core bar. Results indicated that the tensile strength and bending strength of the full-size composite crossarm mandrel experienced minimal changes after aging, remaining well within operational requirements. However, the silicone rubber outer sheath's hydrophobicity decreased, leading to the appearance of cracks and holes on the surface, which provided pathways for moisture and salt infiltration into the mandrel. As a consequence, the bending strength and shear strength of the mandrel material were reduced by 16.5% and 37.7%, respectively. Moreover, the electrical performance test demonstrated a slight change in the mandrel's leakage current, while the electrical breakdown strength decreased by 22.8%. Microscopic analysis using SEM, three-dimensional CT, and TGA revealed that a small amount of resin matrix decomposed and microcracks appeared on the surface. Additionally, the fiber-matrix interface experienced debonding and cracking, leading to an increased moisture absorption rate of the mandrel material.
Related Concept Videos
Distribution Reliability and Automation
Cable Subjected to a Distributed Load
Reclosers and Fuses
A comprehensive protection scheme for radial distribution...
Energy Losses in Transformers
There are four main reasons for energy losses in transformers.
The first cause can be the high resistance of the...
Cable Subjected to Concentrated Loads
Secondary Distribution
In residential areas, 120/240 V single-phase, three-wire service is commonly used for lighting, outlets, and large appliances. Urban areas with high-density loads...