CESA-MCFormer: An Efficient Transformer Network for Hyperspectral Image Classification by Eliminating Redundant

Shukai Liu1, Changqing Yin1, Huijuan Zhang1

  • 1School of Software, Tongji University, Shanghai 201800, China.

PubMed
Summary

Hyperspectral image classification is improved by the novel CESA-MCFormer model. This transformer-based approach effectively extracts key spatial and spectral features, achieving high accuracy with minimal data.

Related Concept Videos

Reducing Line Loss01:18

Reducing Line Loss

In a three-phase circuit, line loss is an indicator of energy dissipated as heat due to the resistance of transmission lines. To address this, incorporating transformers into the system—a step-up transformer at the source and a step-down transformer at the load—is a strategic solution. Two three-phase transformers are introduced to improve this.
With a step-up transformer at the source, the voltage is increased, thereby reducing the current in the transmission lines since power loss...
152
Equivalent Circuits for Practical Transformers01:28

Equivalent Circuits for Practical Transformers

The practical equivalent circuits of single-phase two-winding transformers exhibit significant deviations from their idealized versions due to the inherent properties of winding resistance and finite core permeability. These properties result in real and reactive power losses, affecting the transformer's performance. Understanding these deviations is crucial for designing more efficient transformers.
In a practical transformer, each winding exhibits resistance and leakage reactance. The...
422
Types Of Transformers01:16

Types Of Transformers

Transformers can provide desired voltages to a circuit by modifying the number of turns in the secondary windings.
If the ratio of the number of turns in the secondary winding to that of the primary winding is greater than one, then the transformer is said to be a step-up transformer. In a step-up transformer, the voltage at the secondary winding is greater than the voltage applied at the primary winding.
However, if this ratio is less than one, the transformer is said to be a step-down...
976
Energy Losses in Transformers01:21

Energy Losses in Transformers

In an ideal transformer, it is assumed that there are no energy losses, and, hence, all the power at the primary winding is transferred to the secondary winding. However, in reality,  the transformers always have some energy losses, and, hence, the output power obtained at the secondary winding is less than the input power at the primary winding due to energy losses.
There are four main reasons for energy losses in transformers.
The first cause can be  the high resistance of the...
873
Transformers with Off-Nominal Turns Ratios01:25

Transformers with Off-Nominal Turns Ratios

In scenarios involving parallel transformers with disparate ratings, developing per-unit models requires accommodating off-nominal turns ratios. This situation arises when the selected base voltages are not proportional to the transformer’s voltage ratings. Consider a transformer where the rated voltages are related by the term a. If the chosen voltage bases satisfy a relationship involving term b, term c is defined as the ratio of these bases. This ratio is then substituted into the...
152
Transformers in Distribution System01:27

Transformers in Distribution System

Transformers in distribution systems can be broadly categorized into distribution substation transformers and other distribution transformers. They are crucial for stepping down high transmission voltages to levels suitable for distribution and end-user applications.
Distribution substation transformers come in various ratings and typically use mineral oil for insulation and cooling. To prevent moisture and air from entering the oil, some transformers use an inert gas like nitrogen to fill the...
102